| Plan Review Notes For Permit 07080044 |
| Permit Number |
07080044 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-11-02 14:55:23 | ***DENIED*** | | | | | | IT DOES NOT APPEAR THAT ALL OF THE PREVIOUS FIRE REVIEW | | | COMMENTS HAVE BEEN ADEQUATELY ADDRESSED. | | | | | | 1) THERE IS STILL CONFLICTING ADDRESS INFORMATION ON | | | SHEETS. CORRELATE ALL SHEETS TO ILLUSTRATE CORRECT | | | ADDRESS . | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE | | | SUPPRESSION SYSTEM. SHEET 2 INDICATES A SELF CONTAINED | | | SUPPRESSION SYSTEM. FP 1.00 INDICATES FIRE SPRINKLER | | | COVERAGE. THE FIRE SPRINKLER WORK WOULD HAVE TO BE | | | EXTENDED FROM THE EXISTING BUILDING SYSTEM. PLEASE | | | CLARIFY INFORMATION. | | | | | | 3) THERE APPEARS TO BE AN EXIT DOOR THAT WOULD BE | | | OBSTRUCTED. OTHER SHEETS SHOW AN EXISTING EXTERIOR WALL | | | WITH NO DOOR. | | | | | | 4) PROVIDE DISTANCE OF EQUIPMENT TO WALL AND INDICATE | | | FIRE RATING FOR EXISTING DOOR. | | | | | | 5) SEE COMMENT 3. | | | | | | 6) INCLUDE ADOPTED EDITIONS WHEN REFERENCING NFPA | | | 101,2003, NFPA 33,2003 AND NFPA 17, 2002 IF | | | APPLICABLE. | | | | | | 7) GROUNDING AND BONDING NOTE HAS BEEN ADDED TO PLANS. | | | PLEASE SHOW DETAIL. | | | | | | NEW COMMENT: | | | | | | 1) E1.0 INDICATE THE REMOVEL OF FIRE ALARM DEVICE. WILL | | | IT BE RELOCATED? | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 | | | |
|