| Notes |
| Date |
Text |
| 2007-10-31 13:54:51 | | | | | | | | | | | | | PROVISO | | | | | | IF SPRAY APPLICATION OPERATIONS ARE CONFINED TO AN | | | ENCLOSED SPRAY BOOTH OR ROOM, ANY ELECTRICAL WIRING OR | | | UTILIZATION EQUIPMENT LOCATED WITHIN 3 FT (915 MM) OF | | | ANY OPENING SHALL BE SUITABLE FOR CLASS I, DIVISION 2; | | | CLASSI , ZONE2;OR CLASS II, DIVISION 2 LOCATIONS, | | | WHICHEVER IS APPLICABLE |
|