Plan Review Notes
Plan Review Notes For Permit 07080044
Permit Number 07080044
Review Stop E
Sequence Number 2
Notes
Date Text
2007-10-31 13:54:51 
  
  
  
 PROVISO
  
 IF SPRAY APPLICATION OPERATIONS ARE CONFINED TO AN
 ENCLOSED SPRAY BOOTH OR ROOM, ANY ELECTRICAL WIRING OR
 UTILIZATION EQUIPMENT LOCATED WITHIN 3 FT (915 MM) OF
 ANY OPENING SHALL BE SUITABLE FOR CLASS I, DIVISION 2;
 CLASSI , ZONE2;OR CLASS II, DIVISION 2 LOCATIONS,
 WHICHEVER IS APPLICABLE