| 2007-08-23 18:37:57 | REVIEW #: 1 |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PROVIDE SITE PLAN SHOWING LOCATION OF INTAKE AND |
| | EXHAUST OPENINGS IN RELATION TO PROPERTY LINES, |
| | ADJACENT BUILDINGS AND OPENINGS INTO THIS BUILDING PER |
| | FBC,M 401.5 AND FBC,M 502.7.3.6. |
| | |
| | 2. THIS PERMIT APPLICATION WAS ERRONEOUSLY PROCESSED AS |
| | A MISCELANEOUS PERMIT RATHER THAN A SPRAY BOOTH PERMIT. |
| | AS A RESULT, A REQUIRED FIRE PLAN REVIEW SURCHARGE OF |
| | 10% OF THE PERMIT FEE HAS BEEN ADDED. THIS FEE MUST BE |
| | PAID AT TIME OF RESUBMITTAL. |
| | |
| | 3. WHAT IS THE SOURCE OF MAKE UP AIR FOR THE EXHAUST |
| | FAN IN THE MIXING ROOM? SHOW COMPLIANCE WITH FBC,M |
| | 502.9.5.4. |
| | |
| | 4. PROVIDE WIND LOAD CALCULATIONS SHOWING OUTDOOR |
| | EQUIPMENT AND DUCT RISERS SECURED TO MEET MINIMUM 140 |
| | MPH WIND LOADS IN ACCORDANCE WITH FBC,M 301.13 AND FBC |
| | SEC.1609. SEE FBC 106.1.2. |
| | |
| | 5. PROVIDE DETAIL SHOWING MATERIALS AND FASTENERS TO BE |
| | USED FOR SUPPORTS FOR RISER DUCTS. ALSO SHOW MAXIMUM |
| | SPACING OF SUPPORTS AND METHOD OF ATTACHMENT TO |
| | BUILDING STRUCTURE WHICH MEETS WIND LOAD REQUIREMENTS |
| | AS STATED IN COMMENT #4. |
| | |
| | 6. THE ROOF VIEW ON PG.2 SHOWS TWO 14X28 INTAKE DUCTS |
| | ATTACHED TO TWO 24 INCH DIA. EXHAUST DUCTS. PLEASE |
| | CLARIFY. FBC 106.1.1. |
| | |
| | 7. THIS SYSTEM HAS BEEN DESIGNED BY DIGITAL DESIGN & |
| | DRAFTING. THIS IS NOT A LICENSED ENGINEERING BUSINESS |
| | UNDER THE REQUIREMENTS OF F.S. 471. JF SHANNON, P.E. |
| | STATES ON PLANS THAT HE HAS REVIEWED PLANS FOR CODE |
| | COMPLIANCE AND FOUND THEM TO BE COMPLIANT, INDICATING |
| | HE HAS PROVIDED PLAN REVIEW SERICES AND IS NOT THE |
| | DESIGNER OF RECORD. THERE IS ALSO A NOTE ON THE PLAN |
| | STATING "NOTIFY DIGITAL DESIGN & DRAFTING OF ANY |
| | DESCREPANCY BEFORE PROCEEDING WITH CONSTRUCTION." WHICH |
| | AGAIN INDICATES THEY ARE RESPONSIBLE FOR THE SYSTEM |
| | DESIGN. |
| | |
| | ONE SET OF THESE PLANS IS BEING RETAINED BY THIS OFFICE |
| | FOR POSSIBLE INVESTIGATION BY THE STATE OF FLORIDA FOR |
| | ENGINEERING SERVICES PROVIDED WITHOUT A LICENSE IN |
| | VIOLATION OF FS 471.003. |
| | |