| Plan Review Notes For Permit 07080044 |
| Permit Number |
07080044 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-10-01 17:51:42 | *****DENIED***** | | | | | | | | | 1.THE PROJECT NAME AND ADDRESS ON SHEET 1 IS | | | INCORRECT.THE ACTUAL ADDRESS OF THE PROJECT SITE | | | SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN | | | SHEET. | | | | | | 2.SEPARATE PLANS AND PERMIT REQUIRED FOR THE PAINT | | | BOOTH FIRE SUPPRESSION SYSTEM. | | | | | | 3.THE PROPOSED EQUIPMENT APPEARS TO BE PLACED IN | | | FRONT OF AN EXIT DOOR.WILL THIS DOOR CONTINUE TO BE A | | | MEANS OF EGRESS? | | | | | | 4.PROVIDE THE DISTANCE OF THE EQUIPMENT TO THE WALL | | | AND INDICATE THE FIRE RATING FOR THE EXISTING DOOR. | | | | | | 5.ON SHEET 1, A DOOR IS SHOWN LEADING TO THE PROPOSED | | | SPRAY BOOTH WHEREAS ON SHEET 2, AN EXISTING EXTERIOR | | | WALL IS SHOWN.PLEASE CLARIFY. | | | | | | 6.ON SHEET 2, THE APPROPIATE EDITION OF THE CODES TO | | | BE REFERENCED ARE: NFPA 101- 2003,NFPA 33 - 2003, AND | | | NFPA 17 - 2002. | | | | | | 7.PLEASE INDICATE THE SEPARATION DISTANCE BETWEEN THE | | | INTAKE AND EXHAUST DUCTS.2004 FBC/M 502.7.3.6 | | | | | | 8.ILLUSTRATE REQUIRED GROUNDING AND BONDING FOR THE | | | BOOTH OR ADD TO NOTES THAT THE BOOTH WILL BE PROPERLY | | | GROUNDED AND BONDED. | | | | | | 9.IF TO BE USED, PROVIDE PRODUCT APPROVAL RATING AND | | | SIZE OF SAFETY STORAGE CABINET AND/OR LOCATION OF THE | | | STORAGE AREA. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | | | | | | | | | | | | | | | | |
|