Plan Review Notes
Plan Review Notes For Permit 07080044
Permit Number 07080044
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-17 09:30:07 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ELECTRICAL CONTRACTOR SIGNED ON THE APPLICATION
 IS BANVILLE BARRETT. THE NOTE PROVIDED WITH THE PLANS
 INDICATES "DAVCO ELECTRIC" IS THE INTENDED CONTRACTOR.
 PLEASE CLARIFY, REMOVE BANVILLE FROM THE APPLICATION,
 OR REMOVE THE NOTE.
  
 2} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS,
 CONDUIT AND CONDUCTOR SIZE AND TYPE, AND THE LOCATION
 FOR EQUIPMENT BEING WIRED UNDER THIS PERMIT. FBC
 106.3.5.1.2 AS AMENDED.
  
 3} SEE MECHANICAL AND BUILDING COMMENTS REGARDING
 ENGINEERING AND CONTRACTORS INFORMATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved