| 2007-09-13 16:55:56 | BUILDING PLAN REVIEW |
| | PERMIT: 07080044 |
| | ADD: 4300 N FLAGLER DR |
| | CONT: S L PLOTA CO. LLC |
| | TEL: (727)709-4373 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3)CONTRACTOR S. L. PLOTO CO., LLC NEEDS TO NOTIFY |
| | DBPR OF CHANGE IN ADDRESS FROM WHAT IS CURRENTLY ON |
| | STATE WEB SITE. |
| | |
| | 4) DIGITAL DESIGN & DRAFTING 1 SET OF PLANS HAS BEEN |
| | FORWARDED TO THE STATE OF FLORIDA TO INVESTIGATOR JACK |
| | BEAMISH FLORIDA BOARD OF PROFESSIONAL ENGINEERS FOR |
| | ADVERTISING AS DESIGN PROFESSIONALS WITHOUT LICENSURE. |
| | MR BEMISH REQUESTED THE PLANS FROM THIS PERMIT FOR |
| | ADDITIONAL INFORMATION ON THE CASE # 2007049814 AN |
| | ONGOING INVESTIGATION. FL STATUTE 471. |
| | |
| | 5) SHEET # 1 INDICATES WHAT APPEARS TO BE A OVERHEAD |
| | DOOR TO BE FILLEDIN BY OTHERS? WHO IS PICKING UP THIS |
| | WORK THAT IS NOT UNDER THIS PERMIT? |
| | |
| | 6)SHEET # 2 ONLY PROVIDES A PORTION OF THE REQUIRED |
| | WIND INFORMATION PLEASE COMPLETE: 2004 FL. BLD CODE |
| | 1603.1.4 THE FOLLOWING INFORMATION RELATED TO WIND |
| | SHALL BE SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING CATEGORY 3)- |
| | WIND EXPOSURE |
| | 4)- - COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 7) SHEET# 2 INDICATES THE BASE OF THE EXHAUST DUCTS |
| | SITTING ON A 3'-0" X3'-0" FOUNDATION WITH 3"X3'X1/4" |
| | STEEL ANGLES. ARE THE STEEL ANGLES |
| | FASTENED TO THE EXHAUST DUCT, ? |
| | |
| | 8) SHEET # 2 ALSO INDICATES 2 OF 3 3/16" STEEL CABLES |
| | TO BE SPACED AT 120 DEGREES APART. THE 2 THAT ARE |
| | ILLUSTRATED WILL BE TIED BACK TO THE ROOFING SYSTEM, |
| | WHERE IS THE THIRD CABLE TO BE TERMINATED? 106.1.2* |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 9)SHEET # 2 INDICATES THERE WILL BE (2)24" EXHAUST |
| | DUCTS THAT RUN 6'-0" ABOVE THE ROOF, WILL THE INTAKE |
| | DUCTS ALSO TERMINATE ABOVE THE ROOF? |
| | IT APPEARS THEY ALSOMAY REQUIRE FOUNDATIONS? P[LANS |
| | ARE NOT CLEAR IN THIS MANNER? |
| | |
| | 10)HOW OFTEN WILL THE 24" EXHAUST DUCT BE BRACED BACK |
| | TO THE BUILDING WITH THE 3"X3"X1/4" STEEL ANGLES. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | |
| | |
| | |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |