| Plan Review Notes For Permit 07080036 |
| Permit Number |
07080036 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-08-26 15:18:01 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | | | | SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY | | | | | | 1.HAVE AN ARCHITECT OR ENGINEER CERTIFY THE DECLARED | | | BUILDING HEIGHT OF 60'.DESIGN PRESSURES FOR BUILDINGS | | | OVER 60FEET ARE REQUIRED TO BE DESIGNED USING ASCE7, | | | FBC1609.1.1 AND MUST BE DONE BY A DESIGN PROFESSIONAL. | | | DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED | | | ORIGINALS FAC61G15, FAC61G1 16. | | | | | | 2.PROVIDE A COPY OF THE CONDO ASSOCIATION APPROVAL. | | | | | | 3.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR | | | PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN | | | ANOTHER FORMAT, FBC*106.EDGE DISTANCE AND SHUTTER | | | GLASS SEPARATION COLUMNS WERE LEFT BLANK, SEE SHEET 14. | | | | | | |
|