| Plan Review Notes For Permit 07080030 |
| Permit Number |
07080030 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-08-08 13:14:22 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE | | | GENERATOR | | | INDICATING RECOMMENDED SETBACKS FROM STRUCTURES. | | | | | | 2} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON | | | A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE, | | | DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH | | | ARTICLES 225 AND 230 CAN BE REVIEWED. | | | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR THE | | | PLAN/DRAWINGS, SHALL PRINT AND SIGN THEIR NAME ON THE | | | SHEETS THEY DRAW. PLEASE DO THIS PRIOR TO | | | RESUBMITTING.106.1 FBC AS AMENDED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | | | | |
|