Plan Review Notes
Plan Review Notes For Permit 07071063
Permit Number 07071063
Review Stop B
Sequence Number 1
Notes
Date Text
2007-08-26 16:01:45****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PROVIDE TWO COLLATED SETS FOR PERMIT ISSUANCE.
 THERE APPEAR TO BE TWO SETS BUT PLEASE COLLATE INTO TWO
 DISTINCT SETS; ONE FOR CONTRACTOR, ONE FOR FILE.
  
 2.)SEE OPENING 8.CONNECTION TYPE 6, TOP REQUIRES
 6", BOTTOM REQUIRES 5" SPACING, INSTALLATION SCHEDULE
 SPECIFIED 12"/12".I HAVE HIGHLIGHTED THE PRODUCT
 APPROVAL.
  
 3.)PRODUCT APPROVALS ARE ILLEGIBLE.SOME
 INFORMATION IN THIS CORRECTION LIST MAY BE INCORRECT AS
 I CANNOT READ THE INFORMATION ON THE PRODUCT APPROVAL.
  
 4.)SPANS ARE NOT CORRECT.WALL MOUNT CONNECTIONS
 WOULD RESULT IN A SPAN GREATER THAN THE OPENING
 HEIGHT.
  
 5.)CONNECTION TYPE D, 8' SPAN, REQUIRES 11.5 SPACING
 FOR TAPCONS, SEE OPENING 1 (YOU'D SPECIFIED 12").
 CHECK ALL OPENINGS.
  
  