| Plan Review Notes For Permit 07071062 |
| Permit Number |
07071062 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-10-03 14:51:57 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.)THE ENGINEER HAS SPECIFIED FASTENERS FOR | | | INSULATION BOARD, BUT THE ASSEMBLY IS FOR A NON | | | INSULATED SYSTEM.ENGINEER SHOULD SPECIFY ENHANCED | | | BASE SHEET FASTENING IN ACCORDANCD WITH RAS117.PLEASE | | | HAVE THE ENGINEER CONTACT ME IF HE DISAGREES WITH THIS | | | COMMENT. | | | | | | A SET HAS BEEN RETAINED. |
|