| Notes |
| Date |
Text |
| 2008-04-23 10:43:16 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- FLAT ROOF SYSTEM: REVISE DESIGN PRESSURES SHOWN ON | | | THE RAS 117 CALCULATIONS. SEESTRUCTURAL DRAWING S-4 | | | FOR CORRECT DESIGN PRESSURES CALCULATED BY THE ENGINEER | | | FOR FLAT ROOF AND REVISE AS REQUIRED.THEN, RE-RUN THE | | | RAS 117 CALCULATIONS AND REVISE ANCHOR SPACING AS | | | REQUIRED. | | | | | | 2- REVISE ENERGY CALCULATIONS: | | | A) WALL TYPES ON ITEM #9 NEED TO INCLUDE THE WALL | | | TYPES SHOWN FOR NEW ADDITION AND FOR GARAGE AREA.SEE | | | PLANS AND REVISE AS REQUIRED. | | | | | | NOTE: | | | PROVIDEREVISED INFORMATION AS SOON AS POSSIBLE TO | | | AVOID ANY UNNECESSARY DELAYS OR CONFLICTS DURING | | | INSPECTION. |
|