| Plan Review Notes For Permit 07071040 |
| Permit Number |
07071040 |
|
| Review Stop |
Z |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-03-11 08:58:18 | ***FAILED - RESUB #2*** | | | | | | | | | NEW COMMENTS: | | | | | | 1)PLANS INCONSISTENT.A/C AND POOL EQUIPMENT | | | LOCATION DO NOT MATCH BETWEEN SITE PLAN (A-1) AND MEP | | | PLANS (P-1, M-1, E-1).WHERE IS THE EQUIPMENT TO BE | | | LOCATED?THE EQUIPMENT DOES NOT MEET SETBACK | | | REQUIREMENTS AS SHOWN ON MEP'S, ADDITIONALLY, THE | | | EQUIPMENT SHALL NOT BE PERMITTED WITHIN THE REAR | | | UTILITY EASEMENT OF 5'.PLEASE REVISE PLANS TO BE | | | CONSISTENT AND TO SHOW THE EQUIPMENT WITHIN THE | | | REGULATIONS SET FORTH IN SECTION 94-305 OF THE ZONING | | | AND LAND DEVELOPMENT REGULATIONS. | | | | | | | | | NOTE:DECORATIVE ELEMENTS OF THE FRONT GARDEN WALL | | | SHALL NOT EXCEED 4 FEET 4 INCHES IN HEIGHT, MEASURED | | | FROM GRADE. | | | | | | NOTE:PROPOSED OUTDOOR SHOWER SHALL BE SETBACK A | | | MINIMUM OF 5 FEET FROM THE REAR PROPERTY LINE AND SHALL | | | NOT ENCROACH THE REAR UTILITY EASEMENT. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | | ZONING TECHNICIAN (561)805-6720 | | | | | | | | | | | | | | | SENT TO "E" - BT |
|