Plan Review Notes
Plan Review Notes For Permit 07071040
Permit Number 07071040
Review Stop M
Sequence Number 3
Notes
Date Text
2008-03-14 15:09:09PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R,
 PER 2004 FBC 13-600.3.A, (12-8-06 REVISION).
  
 2) WHEN RESUBMITTING ENERGY CALCULATIONS HAVE THEM
 SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC 13-103.3.
  
 3) PLEASE SUBMIT THE COMPLETE COOLING LOAD CALCULATIONS
 FOR EACH ZONE NOT JUST ONE PAGE FOR THE WHOLE HOUSE,
 PER 2004 FBC 13-607.1.ABC.1.
  
 4) SEE PLAN M-3 RTU MOUNTING DETAIL, STATES 'SEE F.B.C.
 CHAPTER-16 TABLE 1606.1.4 FOR SIZE AND ETC.'. THE 2004
 FBC HAS NO TABLE 1606.1.4 IN CHAPTER 16 PLEASE REMOVE
 FROM PLAN AND PROVIDE AN ENGINEERED DETAIL FOR SECURING
 THE RTU'S TO WITHSTAND WIND LOADS UP TO 140 MPH, PER
 2004 FBC 1609 AND FBC/R M1307.3.
  
 5) PLEASE ADD A NOTE TO THE MECHANICAL PLANS. THE
 MANUFACTURER'S SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS WILL BE ON THE JOB FOR THE INSPECTOR
 SHOWING THE RTU'S ARE DESIGNED TOWITH-STANDING WIND
 LOADS UP TO 140 MPH PER 2004 FBC 1609, OR YOU MAY
 SUBMIT THE MANUFACTURER'S SPEC'S. NOW.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]