| 2008-03-18 17:02:11 | RESIDENTIAL ADDITION AND RENOVATIONS, BUILDING REVIEW |
| | THIRD CHECKLIST. |
| | REVIEW UNDER 2004 FBC WITH 2007 REVISIONS. |
| | |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) FLAT ROOF: NEED TO PROVIDE THE RAS 117 |
| | CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER |
| | AREAS AS REQUIRED BY GENERAL LIMITATION #7.(REPEAT |
| | COMMENT).INFORMATION SUBMITTED ON SHEET A-2 IS THE |
| | EXACT SAME INFORMATION THAT IS PROVIDED IN THE FLAT |
| | ROOF NOA 03-0501.05. |
| | |
| | ***NOTE: COMPONENTS AND CLADDING LOADS SPECIFIED IN THE |
| | STRUCTURAL DRAWINGS NEED TO BE REVISED ACCORDING TO |
| | TABLE R301.2(3),FIGURE R301.2(8) OF 2004 FLORIDA |
| | RESIDENTIALCODE AND THE DEFINITION FOR "EFFECTIVE |
| | WIND AREA"IN THE FBC 2004 SEC. 1609.2. |
| | |
| | ALSO, MINIMUM DIMENSION FOR ZONE "A" IS 4'-0" AS |
| | REQUIRED BY FIGURE R301.2(8). REVISE AS REQUIRED. |
| | |
| | B) FIXED WINDOWS. (REPEAT COMMENT). PRODUCT APPROVAL |
| | SUBMITTED FOR FRENCH DOORS DOESN'T HAVE THE INFORMATION |
| | FOR TRANSOM WINDOWS ABOVE DOORS. |
| | |
| | C) WINDOW/ DOORS MULLIONS. (REPEAT COMMENT). PRODUCT |
| | APPROVAL FOR FRENCH DOORS DOESN'T HAVE THE INFORMATION |
| | FOR MULLIONS. NEED TO PROVIDE SEPARATE PRODUCT |
| | APPROVAL. SEE GENERAL NOTES ON NOA SUBMITTED. |
| | |
| | ALSO, CLEARLY MARK MULLION SIZE AND ATTACHMENT TO |
| | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES. (REPEAT |
| | COMMENT). |
| | |
| | D) GARAGE DOOR SIZE AS SHOWN ON PLANS. (REPEAT |
| | COMMENT). PRODUCT APPROVAL IS FORWIDE DOORS UP TO |
| | 14'-2" .THERE ARE DIFFERENT PRODUCT APPROVALS FOR |
| | NARROWER DOORS. TYPICALLY 8' AND 9' WIDE DOORS. PROVIDE |
| | SUCH PRODUCT APPROVAL.. CONTACT MANUFACTURER FOR PROPER |
| | PRODUCT APPROVAL. |
| | |
| | E) CLAY ROOF TILE.NO PRODUCT APPROVAL SUBMITTED |
| | THIS TIME. |
| | ***NOTE: HISTORIC DISTRICT REQUIRES CLAY TILE. SEE |
| | THEIR COMMENTS IN THE APPROVED DRAWINGS. |
| | NOA 06--0324.01 SPECIFIED BY ARCHITECT ON PRODUCT |
| | APPROVAL REVIEW LIST IS FOR CONCRETE TILE. REVISE AS |
| | REQUIRED. COORDINATE WITH HISTORIC PERSONNEL. |
| | |
| | 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS. SEC. 106.3.3 CITY AMENDMENTS TO |
| | FBC 2004. |
| | |
| | 4- ENERGY CALCULATIONS: |
| | A) PROVIDE CORRECT REVISED FORM. (REPEAT COMMENT). |
| | NEED FORM 600A-2004R. |
| | |
| | B) COMPLETE INFORMATION ON TOP OF FORM. |
| | |
| | C)AREAS SHOWN ON ITEM 6 AND 10A) DON'T MATCH AREAS |
| | SHOWN ON ARCHITECTURAL PLANS.REVISE AS REQUIRED. |
| | |
| | D) R VALUES SHOWN FOR WALLS AND CEILINGS DON'T MATCH |
| | ARCHITECTURAL PLANS. REVISE AS REQUIRED. |
| | |
| | E) WALL TYPE SHOWN ON ITEM 9(A) DOESN'T MATCH |
| | ARCHITECTURAL PLANS. REVISE AS REQUIRED. |
| | NOTE:SEE NEW ADDITION AND GARAGEGUEST ROOM AREA. |
| | |
| | F) ENGINEER TO PROVIDE HIS INFORMATION AS REQUIRED |
| | BY CHAPTER 471 FLORIDA STATUTES AND SEC. 61G15-23.002 |
| | FLORIDA ADMINISTRATIVE CODE. |
| | |
| | G) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. |
| | |
| | 5- PROVIDE DETAILS/SPECIFICATIONS FOR ATTACHMENT OF |
| | STRUCTURAL BUCKS TO BE ATTACHED TO EXISTING AND NEW |
| | COLUMNS. INFORMATION ON SHEET A-10 DOESN'T PROVIDE THIS |
| | INFORMATION. (REPEAT COMMENT). |
| | ARCHITECT RESPONDED THAT THERE IS A DETAIL ON SHEET |
| | A-5. THERE ARE NOT BUCK DETAILS ON THIS SHEET.ALSO, |
| | STRUCTURAL PLANS DON'T ADDRESS THE ISSUE OFBUCK |
| | FASTENING TO THE COLUMNS. SEC. 106.1.2 CITY AMENDMENTS |
| | TO FBC 2004 TO VERIFY COMPLIANCE WITH SEC. R301 AND |
| | R613.6. |
| | |
| | 6- SOIL TEST REPORT: |
| | A) NEED TO PROVIDE REPORTS WITH ORIGINAL SEAL AND |
| | SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES |
| | AND SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 7- SOIL TEST REPORT STATES SOIL BEARING CAPACITY OF |
| | 2000PSF.STRUCTURAL PLANS REQUIRE 2500PSF SOIL BEARING |
| | CAPACITY.STRUCTURAL ENGINEER AND GEO-TECHNICAL |
| | ENGINEER TO COORDINATE INFORMATION AS REQUIRED. |
| | |
| | 8- BRING ALL REVISED DRAWINGS FOR HISTORIC REVIEW AND |
| | APPROVAL PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | |
| | 9- OWES $4.14 FOR NEW ADDITION RADON FEES. |
| | |