| 2007-12-28 13:12:20 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED 2ND TIME: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE STILL |
| | REQUIRED FOR PLUMBING PLAN REVIEW TO MEET CODE |
| | COMPLIANCE. |
| | **NOTE: THERE WAS NOT A TRANSMITTAL LETTER ADDRESSING |
| | PREVIOUS PLUMBING PLAN REVIEW COMMENTS. |
| | |
| | **PREVIOUS REVIEW COMMENTS** |
| | |
| | 1. OK |
| | |
| | 2. **COMMENT NOT ADDRESSED** |
| | SHEET P-1: SPECIFY HOW THE ELECTRIC WATER HEATER IN THE |
| | GARAGE WILL BE PROTECTED FROM MECHANICAL DAMAGE AS |
| | REQUIRED BY FBC, 2004 MECHANICAL, SECTION 303.4. |
| | **SHEET P-1 REVIEW COMMENT REV. #1 INDICATES SEE SHEET |
| | P-3 WATER HEATER DETAIL, HOWEVER SHEET P-3 WATER HEATER |
| | DETAIL ONLY INDICATES TOP OF TANK AT 92". THERE IS NO |
| | INDICATION ON HOW WATER HEATER IS BEING PROTECTED. |
| | PLEASE COMPLY. |
| | |
| | 3. OK |
| | |
| | 4. OK |
| | |
| | 5. **COMMENT NOT ADDRESSED** |
| | SHEET P-2 SANITARY RISER S-2: THE WASHING MACHINE |
| | BRANCH DRAIN AND DRAINAGE STACK ARE SIZED WRONG. PER |
| | *406.3 MINIMUM THREE INCH (3") REQUIRED. |
| | **NOTE: PER *102.1 GENERAL. WHERE, IN ANYSPECIFIC |
| | CASE, DIFFERENT SECTIONS OF THIS CODE SPECIFY DIFFERENT |
| | MATERIALS, METHODS OF CONSTRUCTION OR OTHER |
| | REQUIREMENTS, THE MOST RESTRITIVE SHALL GOVERN. |
| | |
| | 6. OK |
| | |
| | 7. A} OK AND B} OK |
| | |
| | 8. OK |
| | |
| | **THE FOLLOWING ARE NEW COMMENTS** |
| | |
| | 9. SHEET A-1 GUEST ROOM INDICATES A NEW SHOWER AND |
| | SHEETS P-1 AND P-3 ARE INDICATING TUBS. PLEASE |
| | CORRELATE THE PLANS ON THE RESUBMITTAL. PER *106.1.1, |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 10. SHEETS P-1, P-2, AND P-3 ONLY ONE SET OF THESE |
| | SHEETS ARE SIGNED AND SEALED BY ENGINEER OF RECORD |
| | MICHAEL A. TEELE, P. E. #32066. PER *106.1, SUBMITTAL |
| | DOCUMENTS TWO COMPLETE SETS ARE REQUIRED AND THEY SHALL |
| | BE SIGNED AND SEALED PER *CHAPTER 471, FLORIDA |
| | STATUTES. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |