| Plan Review Notes For Permit 07071040 |
| Permit Number |
07071040 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-12-27 08:55:04 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED | | | PER225.32 AT THE MAIN HOUSE. SEE "IMMEDIATE POINT OF | | | ENTRANCE" IN THAT ARTICLE. INDICATE LOCATION ON PLAN | | | PER 230.72(A)(1) | | | | | | 2} THE DINING ROOM ADDITION MUST COMPLY WITH 210.52 | | | RCEPTACLE SPACING REQUIREMENTS. LOCATE ON PLANS. NOTE: | | | IN A DINING ROOM A SMALL APPLIANCE CIRCUIT IS REQUIRED | | | PER 210.52(B)(1). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|