Plan Review Notes
Plan Review Notes For Permit 07071040
Permit Number 07071040
Review Stop E
Sequence Number 2
Notes
Date Text
2007-12-27 08:55:04 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED
 PER225.32 AT THE MAIN HOUSE. SEE "IMMEDIATE POINT OF
 ENTRANCE" IN THAT ARTICLE. INDICATE LOCATION ON PLAN
 PER 230.72(A)(1)
  
 2} THE DINING ROOM ADDITION MUST COMPLY WITH 210.52
 RCEPTACLE SPACING REQUIREMENTS. LOCATE ON PLANS. NOTE:
 IN A DINING ROOM A SMALL APPLIANCE CIRCUIT IS REQUIRED
 PER 210.52(B)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718