Plan Review Notes
Plan Review Notes For Permit 07071040
Permit Number 07071040
Review Stop B
Sequence Number 2
Notes
Date Text
2008-01-04 16:59:50RESIDENTIALADDITION AND RENOVATION, BUILDING REVIEW
 SECOND CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.THIS MAY ME RECORDED AT TIME OF
 PERMIT PICK UP.
  
 2-BRING PLANS TO PALM BEACH COUNTY TO VERIFY IF
 IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE. (REPEAT COMMENT).
  
 3- MISSING DRAWINGS A-2 THRU A-4.ALSO, SET OF PLANS
 SUBMITTED THE FIRST TIME HAD MORETHAN 8 ARCHITECTURAL
 PLANS.PROVIDE 2 COMPLETE SET OF PLANS.
  
 4- PROVIDE PRODUCT APPROVALAS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) FRENCH DOORS "INSWING " AND "OUTSWING" AS SHOWN
 ON PLANS. ALSO, FRENCH DOORS WITH SIDELITES AND TRANSOM
 ABOVE AS SHOWN ON PLANS. (REPEAT COMMENT).FLORIDA
 PRODUCT APPROVAL FL6573 SUBMITTED IS MISSING THE DOORS
 DRAWINGS. PROVIDE COMPLETE PRODUCT APPROVAL INFORMATION
 AND MAKE SURE DOORS INCLUDE THE TYPE OF DOORS SHOWN ON
 PLANS.
  
 B) ARCHED AND RECTANGULAR CASEMENT WINDOWS AS SHOWN
 ON PLANS. (REPEAT COMMENT).FLORIDA PRODUCT APPROVAL
 FL6496 SUBMITTED IS MISSING THE WINDOW DRAWINGS.
 PROVIDE COMPLETEPRODUCT APPROVAL INFORMATION AND MAKE
 SURE WINDOWS INCLUDE THE ONES SHOWN ON PLANS.
  
 C) FIXED WINDOWS,INCLUDING THE ARCHED WINDOWS AS
 SHOWN ON PLANS. (REPEAT COMMENT).
  
 D) WINDOW MULLIONS. AND CLEARLYMARK MULLION SIZE
 ANDATTACHMENT TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER. (REPEAT
 COMMENT).
  
 E) FLAT ROOF.CLEARLY MARKBASE SHEET FASTENING
 OPTION TO BE USEDON PAGE 18 OF NOA 03-0501.05
 SUBMITTED AND PROVIDE RAS 117 CALCULATIONS FOR NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS AS REQUIRED BY
 GENERAL LIMITATION #7. (REPEAT COMMENT).
  
 F)GARAGE DOORS.PROVIDE PRODUCT APPROVAL FOR DOOR
 SIZE AS SHOWN ON PLANS. NOA 06-0331.04 SUBMITTED IS FOR
 14'-2"WIDE DOORS.
  
 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 6- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600.0 FBC 2004. (REPEAT COMMENT). AND MAKE SURE
 CORRECTREVISED FORM IS USED.
  
 7-A) PROVIDE COMPLETE ICYNENE SPECIFICATIONS TO
 VERIFY COMPLIANCE WITHSEC.R314 OF 2004 FLORIDA
 RESIDENTIAL CODE.AND TO CHECK FOR REQUIRED THICKNESS
 TO ACHIEVE SPECIFIED R-VALUES.SEE ENERGY
 CALCULATIONS AND PLANS. (REPEAT COMMENT).
  
 B) PROVIDE DETAIL/SPECS SHOWING HOW TO ACCOMPLISH
 THE R-12 INSULATION WITH ICYNENE INSULATION ON EXISTING
 WALLS.SEEICYNENE SPECIFICATIONS FOR REQUIRED
 THICKNESS.
  
 8- ARCHITECT TO SPECIFY CONSTRUCTION TYPE.INFORMATION
 SUBMITTED IS INCOMPLETE. NEED TO SPECIFY IF
 CONSTRUCTION TYPE V IS A OR B AS REQUIRED BY SEC. 602.1
 FBC 2004.
  
 9- REVISE DIMENSIONS GIVEN FOR NEW STEPSTO COMPLY
 WITH SEC. R311.5.3 OF 2004 FLORIDA RESIDENTIAL CODE.
 GIVEN DIMENSIONS DON'T COMPLY.
  
 10-DESIGNER OF RECORD TO SPECIFY ROOF TILE ATTACHMENT
 AS REQUIRED BY SEC. 106.1.1.2 OF CITY AMENDMENTS TO FBC
 2004.IF USING POLY FOAM, THEN PROVIDE PRODUCT
 APPROVAL. (REPEAT COMMENT).SEE ROOF TILE NOA FOR
 LISTED POLYFOAM TO BE USED.
  
 11-MISSING SHEET A-10. UNABLE TO CHECK IF
 DETAILS/SPECIFICATIONS FORSTRUCTURAL BUCK TO BE
 ATTACHED TO EXISTING AND NEW COLUMNSWERE PROVIDED.
 THIS WAS REQUESTED ON PREVIOUS CHECKLIST. STRUCTURAL
 PLANS DON'T PROVIDE THIS INFORMATION EITHER.
  
 12- SHEET S4:UPDATE REFERENCE STANDARDS. SEE CHAPTER
 43 OF 2004 FLORIDA RESIDENTIAL CODE FOR CORRECT YEAR
 THAT WAS ADOPTED BY THE2004 CODE. (REPEAT COMMENT).
  
 13- PROVIDE SOIL TEST REPORT.SEC. R401.4 OF 2004
 FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT).
  
 14- SHEET S5: REVISE DIMENSIONS GIVEN ON TYPICAL STEP
 FOOTING DETAIL.COORDINATE WITH REVISED DIMENSIONS ON
 ARCHITECTURAL PLAN.STEPS CAN'T HAVE 8" TREADS AND
 RISERS. (REPEAT COMMENT).
  
 15- ARCHITECT TO DATE WHEN SEALING THE PLANS AS
 REQUIRED BY SEC. 61G-16.004 OF FLORIDA ADMINISTRATIVE
 CODE.
  
 16- DRAWINGS ARE MISSING THE DOOR AND WINDOW
 SCHEDULES.
  
 17- BRINGREVISED PLANS TO THECITY HALL 5TH FLOOR
 FOR HISTORICAL APPROVAL AND STAMP PRIOR TO SUBMITTAL TO
 THIS OFFICE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712