2007-08-21 17:00:40DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET P-1: CLEARLY INDICATE THE WATER HEATER SIZE
 IN THE GARAGE AND CLARIFY IF THE WORDING FOR THE GARAGE
 WATER HEATER IS SUPPOSED TO BE"WATER HEATER FOR GUEST
 RM BATH OR GUEST HOUSE."
  
 2. SHEET P-1: SPECIFY HOW THE ELECRIC WATER HEATER IN
 THE GARAGE WILL BE PROTECTED FROM MECHANICAL DAMAGE AS
 REQUIRED BY FBC-2004 MECHANICAL, SECTION 303.4.
  
 3. SHEET P-2: CLEARLY INDICATE THE WATER HEATER SIZE
 IN THE A/C CLOSET AND PER FBC-2004 PLUMBING, SECTION
 504.7 WHERE A WATER HEATER IS INSTALLED ABOVE THE
 GROUND FLOOR THE WATER HEATER SHALL BE INSTALLED IN A
 PAN..
  
 4. SHEET P-2 ELECTRIC WATER HEATER DETAIL: INDICATE
 THERMAL EXPANSION CONTROL PER FBC-2004 PLUMBING
 SECTION, 607.3. (SHEET A-1 IS INDICATING AN EXISTING
 SWIMMING POOL WHICH MEANS A RPZV BACKFLOW PREVENTER IS
 ON POTABLE WATER SERVICE)
  
 5. SHEET P-2 SANITARY RISER S-2: THE WASHING MACHINE
 BRANCH DRAIN OR DRAINAGE STACK IS SIZED WRONG A MINIMUM
 OF 3 INCH IS REQUIRED PER FPC-2004 PLUMBING, SECTION
 406.3.
  
 6. SHEET P-2 SANITARY RISER DIAGRAM: CLEARLY INDICATE
 WHERE THE 1ST FLOOR VENTING FROM BELOW IS LOCATED AND
 WHERE IT TIES INTO THE 2ND FLOOR VENT THRU ROOF
 (V.T.R.) PER FBC-2004 PLUMBING, SECTION 903.3.
  
 7. SHEET P-3 ELECTRIC WATER HEATER SCHEMATIC:
  
 A} INDICATE THERMAL EXPANSION CONTROL PER FBC-2004
 PLUMBING, SECTION 607.3.(SHEET A-1 IS INDICATING AN
 EXISTING SWIMMING POOL WHICH MEANS A RPZV BACFLOW
 PREVENTER IS ON THE POTABLE WATER SERVICE)
  
 B} PER FBC-2004 PLUMBING, SECTION 606.1 A FULL- OPEN
 VALVE SHALL BE INSTALLED ON THE WATER SUPPLY PIPE TO
 THE WATER HEATER.
  
 8. SHEET P-3 SANITARY RISER DIAGRAM: CLEARLY INDICATE
 WHERE THE VENT IS GOING UP TO THE 2ND FLOOR VENT SYSTEM
 FROM THE 1ST FLOOR VENTS PER FBC-2004 PLUMBING, SECTION
 903.3.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK ON
 THE INDICATED PLAN SHEETS BY THIS PLAN EXAMINER FOR
 REFERENCE FOR THE RESUBMITTAL.
  
 END OF COMMENTS:
  