| 2007-08-21 17:00:40 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SHEET P-1: CLEARLY INDICATE THE WATER HEATER SIZE |
| | IN THE GARAGE AND CLARIFY IF THE WORDING FOR THE GARAGE |
| | WATER HEATER IS SUPPOSED TO BE"WATER HEATER FOR GUEST |
| | RM BATH OR GUEST HOUSE." |
| | |
| | 2. SHEET P-1: SPECIFY HOW THE ELECRIC WATER HEATER IN |
| | THE GARAGE WILL BE PROTECTED FROM MECHANICAL DAMAGE AS |
| | REQUIRED BY FBC-2004 MECHANICAL, SECTION 303.4. |
| | |
| | 3. SHEET P-2: CLEARLY INDICATE THE WATER HEATER SIZE |
| | IN THE A/C CLOSET AND PER FBC-2004 PLUMBING, SECTION |
| | 504.7 WHERE A WATER HEATER IS INSTALLED ABOVE THE |
| | GROUND FLOOR THE WATER HEATER SHALL BE INSTALLED IN A |
| | PAN.. |
| | |
| | 4. SHEET P-2 ELECTRIC WATER HEATER DETAIL: INDICATE |
| | THERMAL EXPANSION CONTROL PER FBC-2004 PLUMBING |
| | SECTION, 607.3. (SHEET A-1 IS INDICATING AN EXISTING |
| | SWIMMING POOL WHICH MEANS A RPZV BACKFLOW PREVENTER IS |
| | ON POTABLE WATER SERVICE) |
| | |
| | 5. SHEET P-2 SANITARY RISER S-2: THE WASHING MACHINE |
| | BRANCH DRAIN OR DRAINAGE STACK IS SIZED WRONG A MINIMUM |
| | OF 3 INCH IS REQUIRED PER FPC-2004 PLUMBING, SECTION |
| | 406.3. |
| | |
| | 6. SHEET P-2 SANITARY RISER DIAGRAM: CLEARLY INDICATE |
| | WHERE THE 1ST FLOOR VENTING FROM BELOW IS LOCATED AND |
| | WHERE IT TIES INTO THE 2ND FLOOR VENT THRU ROOF |
| | (V.T.R.) PER FBC-2004 PLUMBING, SECTION 903.3. |
| | |
| | 7. SHEET P-3 ELECTRIC WATER HEATER SCHEMATIC: |
| | |
| | A} INDICATE THERMAL EXPANSION CONTROL PER FBC-2004 |
| | PLUMBING, SECTION 607.3.(SHEET A-1 IS INDICATING AN |
| | EXISTING SWIMMING POOL WHICH MEANS A RPZV BACFLOW |
| | PREVENTER IS ON THE POTABLE WATER SERVICE) |
| | |
| | B} PER FBC-2004 PLUMBING, SECTION 606.1 A FULL- OPEN |
| | VALVE SHALL BE INSTALLED ON THE WATER SUPPLY PIPE TO |
| | THE WATER HEATER. |
| | |
| | 8. SHEET P-3 SANITARY RISER DIAGRAM: CLEARLY INDICATE |
| | WHERE THE VENT IS GOING UP TO THE 2ND FLOOR VENT SYSTEM |
| | FROM THE 1ST FLOOR VENTS PER FBC-2004 PLUMBING, SECTION |
| | 903.3. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK ON |
| | THE INDICATED PLAN SHEETS BY THIS PLAN EXAMINER FOR |
| | REFERENCE FOR THE RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |