Plan Review Notes
Plan Review Notes For Permit 07071040
Permit Number 07071040
Review Stop E
Sequence Number 1
Notes
Date Text
2007-08-20 08:15:57 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
 1} PLEASE PROVIDE A PANEL SCHEDULE SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC
 AS AMENDED. SEE PANEL "A" AND PANEL "C", SHEET E-3, ARE
 INCOMPLETE. NOTE IF ALL SERVICE EQUIPMENT ON THE RISER
 AND PLANS ARE BEING INSTALLED UNDER THIS PERMIT, OR
 WHICH MAY BE EXISTING.
  
 2} AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED
 FROM THE FIRST MEANS OF DISCONNECT TO THE PANEL PER
 250.118, SIZED PER 250.122. NONE IS SHOWN WITH THE
 FEEDER FROM THE 225 AMP MAIN TO PANEL "A".
  
 3}PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, INCLUDING THE GUTTER CONDUCTORS, NIPPLES
 AND CONDUCTORS FEEDING OUT OF THE GUTTER. PANEL "C" IS
 NOTED ON THE PANEL SCHEDULE WHICH IS SUFFICIENT.
  
 4} IN THE ELECTRICAL SPECIFICATIONS, SHEET E-3, NUMBER
 3 C, INDICATES NO CONDUCTORS LARGER THAN THAN #8 MAY BE
 SPLICED. THE 250 MCM ASSUMED TO BE IN THE GUTTER MUST
 BE TAPPED. PLEASE CHECK ALL NOTES FOR RELEVANCE TO THIS
 PROJECT AND REMOVE THE ONES THAT AREN'T, AND CLARIFY
 THE ONES THAT ARE. ALSO SEE THE NOTE ABOUT NO ROMEX
 BEING ALLOWED, (2D). IF NOTES ARE PART OF THE
 CONSTRUCTION DOCUMENTS THEY WILL BE REGARDED AS
 INSTALLATION INSTRUCTIONS BY THE DESIGNER AND MUST BE
 ADHERED TO. ANY FIELD CHANGES WILL NEED TO BE REVISED
 ON THE PLAN AND RESUBMITTED FOR REVIEW.
  
 5} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE THESE
 ALARMS ON THE PLAN.
  
 6} 210.52(C)(2) ISLAND COUNTER SPACES AT LEAST ONE
 RECEPTACLE SHALL BE INSTALLED AT EACH ISLAND COUNTER
 SPACE WITH A LONG DIMENSION OF 600 MM (24 IN.) OR
 GREATER AND A SHORT DIMENSION OF 300 MM (12 IN.) OR
 GREATER. WHERE A RANGETOP OR SINK IS INSTALLED IN AN
 ISLAND COUNTER AND THE WIDTH OF THE COUNTER BEHIND THE
 RANGETOP OR SINK IS LESS THAN 300 MM (12 IN.), THE
 RANGETOP OR SINK IS CONSIDERED TO DIVIDE THE ISLAND
 INTO TWO SEPARATE COUNTERTOP SPACES AS DEFINED IN
 210.52(C)(4). NONE ARE SHOWN FOR THE NEW KITCHEN
 ISLAND. LOCATE ON THE PLAN.
  
 FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN THE
 FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE INDICATE
 THE CODE CYCLES UNDER WHICH THIS PLAN WAS DESIGNED.
 ELECTRICAL SPECIFICATIONS, GENERAL SPECIFICATIONS "D",
 IS VAGUE, AND IN NO WAY INDICATES THE CODES BEING
 REFERRED TO.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718