| 2008-01-03 13:54:45 | 2008-01-03 |
| | |
| | ** DENIED 3RD REVIEW ** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING. |
| | |
| | 1) NOTE: PLEASE SEE COMMENTS FROM PREVIOUS REVIEW WITH |
| | RESPECT TO THE SUBMITTED ENERGY CALCULATIONS AND |
| | COORDINATION WITH PLANS. |
| | PLEASE BE SURE THE FIXTURE LEGEND IS COMPLETE WITH THE |
| | EXTERIOR FIXTURES SUCH AS SITE/PARKING FIXTURES. (THIS |
| | WATTAGE WAS SHOWN ON SITE PLAN.) |
| | PLEASE BE SURE ALL FIXTURE WATTAGES AND NUMBER OF |
| | FIXTURES MATCH. |
| | PLEASE SEE FOR EXAMPLE: PLANS INDICATE A TOTAL OF |
| | 73-64W FIXTURES, YET ONLY 58 -64 W FIXTURES ARE SHOWN |
| | ON THE INPUT DATA REPORT. |
| | PLEASE SEE THE 34 WATT FIXTURES ON THE INPUT DATA |
| | REPORT ARE NOT LOCATED ON PLANS OR FIXTURE LEGEND. (ARE |
| | THESE NOT 64W FIXTURES?) |
| | PLEASE SEE FOR EXAMPLE: THE TOTAL NUMBER OF 32W |
| | RECESSED LIGHTS ON PLANS IS AT 11 AND IDR SHOWS 9. |
| | PLEASE SEE THE LIGHTING TOTAL SHOWN ON E2.1 IS HIGHER |
| | THAN THE TOTAL ON THE IDR. EXAMPLE: PLANS 5408, IDR- |
| | 4510. BOTH ARE LOW. |
| | 13-415.1.A, 13-415.2, 13-415.2.ABC.1.1. .1.2. |
| | |
| | 2) NOTE: PLEASE SEE THE LIGHTING CONTROLS ARE STILL IN |
| | QUESTION AS SHOWN. PLEASE SEE THE LIGHTING PLANS FOR |
| | EXAMPLE SHOWS CORRIDOR LA-16 WHICH SHOWS A NOTE #2 |
| | WHICH MENTIONS TO GO THROUGH LIGHTING CONTACTOR, YET |
| | THE LIGHTING CONTACTOR DOES NOT SHOW LA-16 |
| | PLEASE CLARIFY THE USE OF MANY OF THE LIGHTING CIRCUITS |
| | IN SEPARATE SPACES WHICH GOES THROUGH THE LIGHTING |
| | CONTACTOR SUCH LA-8, LA-36. HOW ARE THESE CONTROLLED BY |
| | THE LIGHTING CONTACTOR YET THE DEVICES IN THE SPACE |
| | DOES NOT SEEM TO BE OVER RIDE(S). PLEASE SEE |
| | 13-415.1.ABC.1.2 WHICH REQUIRES SEPARATE SPACES TO |
| | CONTAIN OVER RIDES. THE SO DEVICES IN OTHER LOCATIONS |
| | ARE SHOWN AS OVER RIDES, HOWEVER THE SWS DOES NOT SEEM |
| | TO SHOW THIS AS A OVER RIDE. |
| | PLEASE CLARIFY. |
| | 13-415.1.ABC.1.1 AND .1.2. |
| | PLEASE SEE THE OWNER AGENT STILL NEEDS TO SIGN NEW |
| | CALCULATIONS ONCE RESUBMITTED. |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT WITH |
| | RESPECT TO FS 553.80(2)(B) AND REPEAT COMMENTS FOR CODE |
| | COMPLIANCE. |
| | PLEASE SEE THE SAME CODE SECTIONS ABOVE FOR CHAPTER 13 |
| | APPLY FOR THE THIRD TIME. |
| | PLEASE BE SURE TO GO OVER PLANS AND COORDINATE ALL. |
| | PLEASE SEE THE FEE AS REQUIRED UNDER THE FLORIDA |
| | STATUTES WAS ASSESSED AND IS DUE BEFORE PLANS MAY BE |
| | RE-SUBMITTED. PLEASE KNOW THAT THE RE-SUB WILL NOT BE |
| | DUE WHEN RE-SUBMITTING. |
| | SHEETS E0.1, 2.1 AND 5.1 HAVE BEEN RETAINED ALONG WITH |
| | ONE COPY OF THE ENERGY CALCULATIONS SUBMITTED. |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| 2008-01-03 13:53:18 | 2008-01-02 |
| | |
| | NEW ELECTRICAL AND LANDSCAPE SHEETS SUBMITTED. |
| 2008-01-01 16:50:44 | 2008-01-01 16:50:44 |
| | |
| | PLANS IN ELECTRICAL FOR REVIEW. |
| | |