| Date |
Text |
| 2007-10-30 09:55:49 | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | *** PLEASE SEE THERE ARE ITEMS FROM PREVIOUS REVIEW |
| | WHICH ARE STILL IN NEED OF ADDRESSING. |
| | PLEASE SEE THAT SOME OF THE EXACT SAME COMMENTS FROM |
| | PREVIOUS REVIEW ARE BELOW. |
| | PLEASE SEE NEW COMMENT BELOW. |
| | |
| | |
| | 1) NOTE: PLEASE SEE LANDSCAPE PLANS AND FS 481.319 FOR |
| | MISSING CERTIFICATE OF AUTHORIZATION NUMBER. |
| | ** THIS IS BEING NOTED ** |
| | |
| | |
| | 2) NOTE: PLEASE SEE COMMENT NUMBER 6 FROM PREVIOUS |
| | REVIEW WHICH IS BEING ATTACHED BELOW AND LABELED AS |
| | **PREVIOUS REVIEW NOTE **. |
| | MANY OF THE SAME ITEMS FROM PREVIOUS REVIEW ARE THE |
| | SAME. |
| | PLEASE SEE THE LIGHTING CONTROLS ARE NOT COMPLETE AND |
| | IN FACT THERE ARE SEVERAL LOCATIONS WHICH STILL |
| | INDICATE A STANDARD SWITCH FOR CONTROL. |
| | PLEASE SEE THE LIGHTING BEING CONTROLLED MUST BE SEEN |
| | BY THE OCCUPANT WHICH IS CONTROLLING THE LIGHTING. |
| | PLEASE SEE SHEET E2.1 WHICH CONTAINS A KEY NOTE #2 |
| | WHICH MENTIONS TO SEE E0.1 FOR DETAIL, YET E0.1 DOES |
| | NOT CONTAIN ANY DETAIL FOR ANY LIGHTING CONTROLS. |
| | PLEASE SEE THE LIGHTING ON PLANS DOES NOT CORRELATE |
| | WITH THE FIXTURE LEGEND FOR ALL FIXTURES AND DOES NOT |
| | CORRELATE WITH THE INPUT DATA REPORT ON THE SUBMITTED |
| | ENERGY CALCULATIONS. FOR EXAMPLE: SEE EXTERIOR LIGHTING |
| | AS NONE ARE SHOWN ON FIXTURE LEGEND. FOR EXAMPLE: SEE |
| | INTERIOR LIGHTING AS THE WATTAGES IS NOT THE SAME. FOR |
| | EXAMPLE: COVER SHEET ON ENERGY CALCULATIONS STILL CALL |
| | FOR THIS AS A *SHELL BUILDING*. HOW IS THIS POSSIBLE |
| | WHEN PLANS DO NOT INDICATE A SHELL BUILDING??? |
| | PLEASE BE SURE THE OWNER AGENT IS SIGNED ON |
| | CERTIFICATION SHEETS. |
| | PLEASE SEE THERE ARE SEVERAL ITEMS AS NOTED ABOVE FOR |
| | EXAMPLE ALONG WITH MOST OF THE SAME COMMENTS BELOW FROM |
| | PREVIOUS REVIEW WHICH NEED TO BE ADDRESSED. |
| | |
| | ** PREVIOUS REVIEW NOTE #6 *** |
| | PLEASE SEE THE FOLLOWING NOTES FOR FBC CHAPTER 13. |
| | PLEASE INDICATE LIGHTING CONTROLS PER |
| | 13-415.1.ABC.1.1, .1.2. |
| | PLANS INDICATE A TIME CLOCK HOWEVER LOCATIONS FOR ALL |
| | OVER RIDES AS REQUIRED COULD NOT BE FOUND ON PLANS. |
| | PLEASE SEE THERE IS SEPARATE SPACE CONTROL MISSING FOR |
| | MANY AREAS. |
| | PLEASE SEE NO TIME SCHEDULING WAS SUBMITTED. PLEASE SEE |
| | NO MAXIMUM OVER RIDE TIMES WERE INDICATED (DEVICES NOT |
| | SHOWN) |
| | PLEASE BE SURE ALL DEVICES WHICH WILL BE IN DESIGN AND |
| | ON PLANS ARE STATED ON LEGEND FOR DEVICES. |
| | PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO NOT |
| | CORRELATE WITH THE PLANS AND DESIGN. THESE INDICATE |
| | BUILDING BEING A *SHELL* WHEN IN FACT THE BUILDING IS |
| | BEING BUILT OUT AT THIS TIME. PLEASE ALSO SEE THE INPUT |
| | DATA REPORT DOES NOT CORRELATE WITH PLANS. |
| | PLEASE SEE THE TYPE OF FIXTURES. |
| | PLEASE SEE THE NUMBER OF FIXTURES |
| | PLEASE SEE THE WATTAGE OF FIXTURES. |
| | PLEASE SEE NO EXTERIOR LIGHTING WAS INPUTTED IN THE IDR |
| | WHEN THE PLANS CONTAIN EXTERIOR LIGHTS. |
| | PLEASE BE SURE THE METHOD OF CONTROLS IS COORDINATED |
| | WITH PLANS AND DESIGN FOR THE METHOD OF CONTROL. SHOWN |
| | AS *MANUAL ON/OFF* WHICH IS NOT POSSIBLE AS THE PLANS |
| | ARE REQUIRED AND CONTAIN AUTOMATED CONTROLS. |
| | THERE ARE SEVERAL ITEMS ON THE CALCULATIONS WHICH NEED |
| | TO BE ADDRESSED. |
| | |
| | PLEASE SEE MECHANICAL REVIEW COMMENTS WITH RESPECT TO |
| | ENERGY CALCULATIONS. PLEASE BE SURE THE INPUT DATA |
| | COORDINATES WITH THE PLANS. |
| | PLEASE PROVIDE LIGHTING POWER PERFORMANCE CALCULATIONS |
| | PER 13-415.2. |
| | PLEASE KNOW AT THIS TIME NO REVIEW FOR LIGHTING |
| | COMPLIANCE CAN BE DONE FOR INTERIOR AND EXTERIOR |
| | LIGHTING POWER ALLOWANCES. PLEASE SEE 13-415.2, |
| | 13-415.2.ABC.1.2, 13-415.2.ABC.1.3, 13-415.2.ABC.1.1 |
| | |
| | 3) NOTE: PLEASE SEE THIS COMMENT FROM PREVIOUS REVIEW |
| | WILL REMAIN AS NOT ALL FIXTURES ON CALCULATIONS, |
| | FIXTURE LEGEND AND PLANS ARE THE SAME. |
| | FBC 106.1.2 FOR COORDINATION/ADDITIONAL INFORMATION. |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE COMPLETE ALL FIXTURE DESIGNATIONS ON PLANS AND |
| | CORRELATE WITH THE LEGEND. |
| | PLEASE SEE SOME FIXTURES COULD NOT BE IDENTIFIED FOR |
| | EMERGENCY USE ALTHOUGH THIS IS ONLY ASSUMED AT THIS |
| | TIME DUE TO THE SHADING ON PLANS. |
| | |
| | 4) NOTE: PLEASE SEE DISCONNECTS LOCATED OUTSIDE FOR THE |
| | CONDENSING UNITS DO NOT MEET 110.26 FOR MINIMUM WIDTHS |
| | OR DEPTHS. THIS IS THE SAME COMMENT. BASED ON THE PLANS |
| | AND SCALE ON SHEETS, THESE DO NOT MEET THE MINIMUM |
| | 30X36 INCHES REQUIRED. |
| | PLEASE ADJUST AND PLEASE BE SURE TO ADJUST OTHER SHEETS |
| | FOR RELEVANT SET-BACKS AND DIMENSIONS. |
| | |
| | 5) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOE CODE COMPLIANCE. THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME. |
| | ONE COPY OF ELECTRICAL PLANS AND ENERGY CALCULATIONS |
| | HAVE BEEN RETAINED. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-10-29 16:38:33 | |
| | |
| | IN ELEC FOR REVIEW. |