| 2007-08-24 17:22:38 | REVIEW #: 1 |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. M0.1 MECH NOTES #12: THERMOSTATIC CONTROLS SHALL |
| | COMPLY WITH FBC 13-407.1.ABC.2.4.1. |
| | |
| | 2. M0.1 AIR BALANCE SCHEDULE: AHU #5 IS MISSING FROM |
| | THE SCHEDULE. PLEASE CORRECT AND RESUBMIT. |
| | |
| | 3. M0.1 FAN SCHEDULE: CONTROLS INDICATE "LIGHT |
| | INTERLOCK." PROVISIONS SHALL ALSO BE MADE TO INTERLOCK |
| | FANS WITH AHU #4 TO ASSURE THAT ALL AIR SUPPLIED TO THE |
| | TOILET ROOMS IS EXHAUSTED AND NOT RECIRCULATED IN |
| | ACCORDANCE WITH FBC,M 403.2.1(3). |
| | |
| | 4. M2.1: AHU #4 ON FLOOR PLAN SHOWS 1330 CFM WHILE AHU |
| | #5 SHOWS 1050 CFM. EQUIPMENT SCHEDULE CALLS FOR 1200 |
| | CFM EACH. PERHAPS ONE OR MORE DROPS IS ATTACHED TO THE |
| | WRONG SYSTEM. SHOW AN AIR BALANCE WHICH IS IN |
| | CONJUNCTION WITH EQUIPMENT SCHEDULE. |
| | |
| | 5. M5.1: DUCT SMOKE DETECTORS SHALL BE CONNECTED TO THE |
| | BUILDING FIRE ALARM SYSTEM PER FBC,M 606.4.1. |
| | |
| | 6. M5.1: LOUVER DETAIL INDICATES A MIAMI-DADE NOA WHICH |
| | HAS EXPIRED. PROVIDE AN UPDATED FLORIDA PRODUCT |
| | APPROVAL OR NOA SUBMITTAL. |
| | |
| | 7. M5.1: AHU DETAIL SHOWS LOUVERED DOORS BUT FLOOR PLAN |
| | SHOWS SOLID DOORS WITH WALL GRILL. PLEASE COORDINATE |
| | PLANS. |
| | |
| | 8. ENERGY CALCULATIONS: THIS SPACE IS NOT COOLED BY ONE |
| | SYSTEM OF 240,000 TO 760,000 BTU/H COOLING CAPACITY. |
| | ADJUST CALCULATIONS TO ACCURATELY REFLECT THE EQUIPMENT |
| | BEING USED AND THE MINIMUM EFFICIENCY RATING REQUIRED. |
| | EXAMPLE: FOR EQUIPMENT <65,000 BTU/H THE EFFICIENCY |
| | CRITERIA IS 13.00 NOT 9.50 AS STATED ON CALCULATIONS |
| | SYSTEM REPORT. |
| | |
| | 9. ROOF TYPE ON INPUT DATA REPORT SHOWS A METAL |
| | BUILDING ROOF WITH R-19 BATTS. THIS IS NOT A METAL |
| | BUILDING AND THERE ARE NO BATTS AT THE ROOF. PLEASE |
| | CORRECT TO ACCURATELY REFLECT THE SYSTEM BEING USED ON |
| | THIS BUILDING AND RESUBMIT. |
| | |