| 2007-09-25 15:41:58 | *****DENIED***** |
| | |
| | |
| | 01.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK |
| | OF EACH SUBMITTED PLAN SHEET. |
| | |
| | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 03.THE SCOPE OF WORK SHALL IN NO WAY INTERFERE OR |
| | HINDER EMERGENCY ACCESS TO THE PROPERTY OR VICINITY |
| | THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES). |
| | |
| | 04.PLEASE INCLUDE EXIT LIGHTS AND FIRE EXTINGUISHERS |
| | ON THE FLOOR PLAN (A-201). |
| | |
| | 05.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE |
| | INSTALLATION OF THE FIRE ALARM SYSTEM. |
| | |
| | 06.IT IS INDICATED THAT THE BUILDING WILL BE EQUIPPED |
| | WITH A KNOX BOX;FOR APPLICATIONS CONTACT WEST PALM |
| | BEACH FIRE PREVENTION BUREAU AT 561-804-4724. |
| | |
| | 07.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS |
| | SOUTHERN BOULEVARD, SHOW THE ADDRESS NUMBERS ON THE |
| | BUILDING.AS PER WEST PALM BEACH CODE, THE NUMBERS |
| | SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" |
| | IN WIDTH. |
| | |
| | 08.ON SHEET FA0.1 AMEND FIRE ALARM NOTE #17 AS SUCH: |
| | DELETE "SUPERVISORY SIGNAL ONLY"-INSERT "GENERAL |
| | FIRE ALARM".AS PER LOCAL REQUIREMENTS, DUCT SMOKE |
| | DETECTORS SHALL INITIATE A GENARAL FIRE ALARM. |
| | |
| | 09.ON SHEET A-901, ADD TO DOOR REMARKS AS NOTE 6:A |
| | DOOR NORMALLY REQUIRED TO BE KEPT CLOSED SHALL NOT BE |
| | SECURED IN THE OPEN POSITION AT ANY TIME AND SHALL BE |
| | SELF CLOSING OR AUTOMATIC CLOSING IN ACCORDANCE WITH |
| | 7.2.1.8.2 OF NFPA 101 - 2003 EDITION. |
| | |
| | 10. ON SHEET A-901,PLEASE EXPLAIN DOOR REMARK #2 IN |
| | REFERENCE TO DOORS 124 AND 125 AS LOCATED ON A-201. |
| | WILL A PERSON OR PERSONS BE ABLE TO EGRESS FROM THESE |
| | AREA ONCE INSIDE WITHOUT A KEY, A TOOL, OR SPECIAL |
| | KNOWLEDGE? |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE ON THE PLAN EACH COMMENT |
| | WAS ADDRESSED |
| | |
| | |