| Date |
Text |
| 2007-08-25 19:54:09 | 2007-08-25 19:54:09 |
| | |
| | *** DENIED *** |
| | |
| | ** PLEASE KNOW AS SOME INFORMATION WAS NOT YET |
| | SUBMITTED A COMPLETE AND FULL REVIEW FOR SOME ITEMS |
| | COULD NOT BE DONE. |
| | |
| | ** PLEASE SEE THERE ARE SEVERAL COMMENTS BELOW (2,3,4 |
| | AND 5) WHICH DO NOT PERTAIN TO KAMM CONSULTING |
| | ENGINEERING. |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED |
| | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS |
| | NOT MADE BY OTHER TRADE(S). |
| | |
| | 2) NOTE: PLEASE SEE MISSING INFORMATION ON THE TITLE |
| | BLOCKS FOR THE LANDSCAPE PLANS. |
| | PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER |
| | AND INFORMATION AS REQUIRED PER 61G1-16.004. PLEASE SEE |
| | FS 481.219 FOR REQUIRED MISSING CA #. |
| | |
| | 3) NOTE: PLEASE SEE ALL SHEETS OF THE SUBMITTED |
| | LANDSCAPE PLANS ARE IN FACT *PHOTO-COPIES* OF SIGNED |
| | AND SEALED PLANS. |
| | PLEASE BE SURE TO SIGN, DATED AND SEALED PLANS WITH THE |
| | REQUIRED RAISED SEAL AND ORIGINAL SIGNATURE. PLEASE SEE |
| | FS 481.221, AND PLEASE SEE FAC 61G1-16.002 FOR CORRECT |
| | SEAL AS REQUIRED. |
| | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADE(S). |
| | |
| | 4) NOTE: PLEASE SEE THE CIVIL PLANS SUBMITTED ARE NOT |
| | SIGNED, DATED AND SEALED AS REQUIRED PER FAC |
| | 61G15-23.002, FS 471.025 |
| | PLEASE ALSO SEE MISSING INFORMATION AS REQUIRED ON |
| | TITLE BLOCKS ARE REQUIRED PER FAC 61G15-23.002. |
| | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADE(S). |
| | |
| | 5) NOTE: PLEASE SEE MISSING INFORMATION ON THE TITLE |
| | BLOCKS ON THE *S* SHEETS. |
| | PLEASE SEE MISSING PRINTED NAME, PRINTED LICENSE NUMBER |
| | AND MISSING CERTIFICATE OF AUTHORIZATION NUMBER AS |
| | REQUIRED PER FAC 61G15-23.002, FS 471.023 |
| | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADES. |
| | |
| | 6) NOTE: PLEASE SEE THE FOLLOWING NOTES FOR FBC CHAPTER |
| | 13. |
| | PLEASE INDICATE LIGHTING CONTROLS PER |
| | 13-415.1.ABC.1.1, .1.2. |
| | PLANS INDICATE A TIME CLOCK HOWEVER LOCATIONS FOR ALL |
| | OVER RIDES AS REQUIRED COULD NOT BE FOUND ON PLANS. |
| | PLEASE SEE THERE IS SEPARATE SPACE CONTROL MISSING FOR |
| | MANY AREAS. |
| | PLEASE SEE NO TIME SCHEDULING WAS SUBMITTED. PLEASE SEE |
| | NO MAXIMUM OVER RIDE TIMES WERE INDICATED (DEVICES NOT |
| | SHOWN) |
| | PLEASE BE SURE ALL DEVICES WHICH WILL BE IN DESIGN AND |
| | ON PLANS ARE STATED ON LEGEND FOR DEVICES. |
| | PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO NOT |
| | CORRELATE WITH THE PLANS AND DESIGN. THESE INDICATE |
| | BUILDING BEING A *SHELL* WHEN IN FACT THE BUILDING IS |
| | BEING BUILT OUT AT THIS TIME. PLEASE ALSO SEE THE INPUT |
| | DATA REPORT DOES NOT CORRELATE WITH PLANS. |
| | PLEASE SEE THE TYPE OF FIXTURES. |
| | PLEASE SEE THE NUMBER OF FIXTURES |
| | PLEASE SEE THE WATTAGE OF FIXTURES. |
| | PLEASE SEE NO EXTERIOR LIGHTING WAS INPUTTED IN THE IDR |
| | WHEN THE PLANS CONTAIN EXTERIOR LIGHTS. |
| | PLEASE BE SURE THE METHOD OF CONTROLS IS COORDINATED |
| | WITH PLANS AND DESIGN FOR THE METHOD OF CONTROL. SHOWN |
| | AS *MANUAL ON/OFF* WHICH IS NOT POSSIBLE AS THE PLANS |
| | ARE REQUIRED AND CONTAIN AUTOMATED CONTROLS. |
| | THERE ARE SEVERAL ITEMS ON THE CALCULATIONS WHICH NEED |
| | TO BE ADDRESSED. |
| | |
| | PLEASE SEE MECHANICAL REVIEW COMMENTS WITH RESPECT TO |
| | ENERGY CALCULATIONS. PLEASE BE SURE THE INPUT DATA |
| | COORDINATES WITH THE PLANS. |
| | PLEASE PROVIDE LIGHTING POWER PERFORMANCE CALCULATIONS |
| | PER 13-415.2. |
| | PLEASE KNOW AT THIS TIME NO REVIEW FOR LIGHTING |
| | COMPLIANCE CAN BE DONE FOR INTERIOR AND EXTERIOR |
| | LIGHTING POWER ALLOWANCES. PLEASE SEE 13-415.2, |
| | 13-415.2.ABC.1.2, 13-415.2.ABC.1.3, 13-415.2.ABC.1.1 |
| | |
| | 7) NOTE: PLEASE COMPLETE ALL FIXTURE DESIGNATIONS ON |
| | PLANS AND CORRELATE WITH THE LEGEND. |
| | PLEASE SEE SOME FIXTURES COULD NOT BE IDENTIFIED FOR |
| | EMERGENCY USE ALTHOUGH THIS IS ONLY ASSUMED AT THIS |
| | TIME DUE TO THE SHADING ON PLANS. |
| | |
| | 8) NOTE: PLEASE KNOW THAT THE PLANS NEED TO LABEL AND |
| | PROVIDE ROOM AND AREA DESIGNATIONS ON PLANS AND |
| | CORRELATE WITH THE PANEL SCHEDULES SHOWING ALL ROOMS |
| | AND AREAS IN WHICH CIRCUITS FEED WILL BE REQUIRED FOR |
| | EACH PANEL. PLEASE SEE THE USE OF *RECEPTACLES AND |
| | LIGHTING * ON PANEL SCHEDULE DOES NOT PROVIDE THE |
| | DETAILED INFORMATION NEEDED. |
| | PLEASE KNOW THESE CAN BE ALPHA OR NUMERIC DESIGNATIONS |
| | IF THIS HELPS TO ALLEVIATE CONGESTION ON PLANS.PLEASE |
| | SEE TEXT WHICH IS TAKEN FROM COMMENTARY IN THE CODE |
| | WHICH STATES THE USE OF *GEN LT* ETC IS NOT |
| | ACCEPTABLE. |
| | |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 9) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS INDICATES |
| | THE FPL TRANSFORMER IN ONE LOCATION AT THE REAR OF THE |
| | PROPERTY AND THE ELECTRICAL PLANS INDICATES THIS SAME |
| | TRANSFORMER AT THE FRONT ENTRANCE. |
| | THIS LOCATION CONTAINS THE FPL POLES AT THE REAR OF |
| | PROPERTY. PLEASE COORDINATE AND ADJUST PLANS. |
| | FBC 106.1.2 |
| | |
| | 10) NOTE: PLEASE SEE MISSING SIGN CIRCUIT REQUIRED AT |
| | THE FRONT ENTRANCE PER 600.5. |
| | PLEASE BE SURE TO ADJUST THE CALCULATIONS TO THE |
| | MINIMUM LOAD OF 1200 VA. |
| | |
| | 11) NOTE: PLEASE CLARIFY THE REQUIRED DISCONNECTING |
| | MEANS FOR AIR HANDLER UNITS INSIDE BUILDING PER |
| | 440.11. |
| | |
| | 12) NOTE: PLEASE SEE DISCONNECTS LOCATED OUTSIDE FOR |
| | THE CONDENSING UNITS DO NOT MEET 110.26 FOR MINIMUM |
| | WIDTHS OR DEPTHS. |
| | PLEASE ADJUST. |
| | |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |