2007-09-22 06:55:14DENIED
 REFERENCE: FBC-2004 PLUMBING
 CITY WPB MUNICIPAL CODE
  
 1. SHT 1 OF 6 INDICATES 4" WASTE TO STORM. THIS NOT
 APPROVED. WASTE FROM THE FILTER SHALL DRAIN TO
 SANITARY. ARTICLE III SECTION 90-123(B). PLEASE CORRECT
 DRAINAGE TO REFLECT THE REQUIREMENT.
  
 2. SHT 4 OF 6 INDICATES COLLECTOR TANK OVERFLOW TO
 WASTE. THIS IS NOT APPROVED. OVERFLOW SHALL DRAIN TO
 STORM. ARTICLE III SECTION 90-125(5). PLEASE CORRECT
 DRAINAGE TO REFLECT THE REQUIREMENT.
  