Plan Review Notes
Plan Review Notes For Permit 07071029
Permit Number 07071029
Review Stop E
Sequence Number 1
Notes
Date Text
2007-08-23 18:43:26 
 *** DENIED***
  
 1) NOTE: PLEASE SUBMIT ELECTRICAL DETAILS FOR ALL POOL
 EQUIPMENT. PLEASE INDICATE PUMPS, SIZES, CONDUCTORS,
 OVER CURRENT PROTECTION ETC.
 PLEASE INCLUDE THE SAME FOR LIGHT(S).
 PLEASE SUBMIT INFORMATION WHERE PUMPS AND OTHER
 ELECTRICAL EQUIPMENT IS BEING FED FROM. PLEASE INCLUDE
 THE PANEL SCHEDULE FOR THESE ITEMS.
 408.4, 240.4, 310.16 ETC.
 FBC 106.1.2, 106.3.5.1.2
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS AS REQUIRED.
 2005 NFPA-70
 2004 FBC W/2006 REVISIONS.
  
  
 *** AS COMPLETED ELECTRICAL INFORMATION WAS NOT
 SUBMITTED, A FULL REVIEW COULD NOT BE DONE.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]