| Plan Review Notes For Permit 07071009 |
| Permit Number |
07071009 |
|
| Review Stop |
M |
| Sequence Number |
8 |
|
| Notes |
| Date |
Text |
| 2008-10-11 14:16:52 | REVIEW #: 4TH FOR THIS REVISION | | | ACTION: PROVISO | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | REVISED PAGES M-1A, M-1B, M-2, M-3 | | | | | | ***************PROVISO******************* | | | PROVIDE DOCUMENTATION FROM RTU MANUFACTURER SHOWING | | | THESE APPLIANCES ARE DESIGNED AND CONSTRUCTED TO RESIST | | | ANTICIPATED WIND PRESSURES IN ACCORDANCE WITH FBCM | | | 301.13 AND FBCB 1609.1. SUCH DOCUMENTATION SHALL BE | | | SUBMITTED FOR A PASSED PLAN REVIEW PRIOR TO FINAL | | | MECHANICAL INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|