2008-09-10 08:53:21REVIEW #: 2ND FOR REVISION 3
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. THE FOLLOWING ISSUES RELATED TO RATED WALLS AND DUCT
 PENETRATIONS ARE STILL OUTSTANDING:
  
 A) PAGE M-1A IS STILL MISSING AT LEAST ONE FIRE DAMPER
 AT THE 12X12 DUCT PENETRATION OF THE WALL BETWEEN ROOM
 #7 AND ROOM #138. THERE IS STILL A FIRE DAMPER SHOWN ON
 THE PLANS IN THE 6 INCH ROUND DUCT AT THE NON-RATED
 WALL BETWEEN ROOM #130 AND THE MAIN LOBBY.
 PAGE M-1B IS STILL MISSING ONE FIRE DAMPER IN THE 24X12
 DUCT PENETRATION OF THE WALL BETWEEN ROOM #7 AND ROOM
 #138.
  
 B) OK
  
 C) PAGE M-2: FIRE/SMOKE DAMPERS HAVE BEEN REMOVED FROM
 PLANS. HOWEVER, THE PLANS DO NOT SHOW PROVISIONS FOR
 FAN SHUT-DOWN BY DUCT SMOKE DETECTOR AS REQUIRED IN
 ACCORDANCE WITH FBCM 606.2. SHOW COMPLIANCE WITH THIS
 SECTION.
  
 2 AND 3: OK
  
 4. PAGE M-3: ONE OF THE TWO ROOF CURB DETAILS WHICH
 WERE PASTED ONTO THIS PAGE IS SMALL AND ILLEGIBLE.
 ALSO, BOTH OF THE CURB DETAILS ARE IN CONFLICT WITH THE
 STRUCTURAL DETAILS FOR ROOF CURB INSTALLATION. SEE PAGE
 SD-3. ALSO, THE RTU TIE-DOWN DETAIL SHOWS CABLES
 ATTACHING TO SOME SORT OF CONCRETE EMBEDDED ANCHORING
 SYSTEM INSTALLED IN A CONCRETE SLAB. HOW IS THIS
 INSTALLATION POSSIBLE ON A ROOF WHICH CONSISTS OF A
 BUILT-UP ROOF SYSTEM ON A STEEL DECK OVER BAR JOISTS?
 THIS IS THE TYPE OF ROOFING SYSTEM SHOWN ON STRUCTURAL
 PLANS. CLARIFY AND COORDINATE STRUCTURAL AND MECHANICAL
 DRAWINGS. ADDITIONALLY, STILL NO INFORMATION WAS
 PROVIDED FROM THE RTU OR EXHAUST FAN MANUFACTURERS
 SHOWING THEIR APPLIANCES ARE DESIGNED TO RESIST WIND
 PRESSURES. MECHANICAL EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST THE WIND PRESSURES ON THE EQUIPMENT
 AND THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH FBCM
 301.13.
  
 5 AND 6: OK
  
 7. COOLING LOAD CALCULATIONS IN THE FORM OF A SYSTEM
 SIZING SUMMARY HAVE BEEN PROVIDED AS REQUESTED.
 HOWEVER, ALSO SUBMITTED WAS 3 COPIES OF ENERGY
 CALCULATIONS FOR WHAT APPEARS TO BE ANOTHER PROJECT
 LOCATED IN ANOTHER JURISDICTION. WHAT IS THE PURPOSE OF
 INCLUDING THESE CALCULATIONS WITH THIS SUBMITTAL?
 PLEASE CLARIFY.
 NOTE: A COMPLETE ENERGY CODE COMPLIANCE FORM IS NOT
 REQUIRED FOR THIS PROJECT. ONLY COMPLIANCE WITH THE
 BASIC PRESCRIPTIVE REQUIREMENTS IS NECESSARY IN
 ACCORDANCE WITH FBCB 13-101.6.
  
 NOTE: PLEASE RESPOND TO EACH COMMENT IN WRITING WITH A
 DESCRIPTION OF HOW EACH COMMENT HAS BEEN ADDRESSED AS
 WELL AS WHERE THE INFORMATION CAN BE FOUND. REMOVE
 OLD/VOIDED SHEETS FROM THE SUBMITTED PLANS AND PROVIDE
 ONE SET OF OLD VOIDED/SHEETS FOR REFERENCE.
  