Plan Review Notes
Plan Review Notes For Permit 07071009
Permit Number 07071009
Review Stop M
Sequence Number 6
Notes
Date Text
2008-08-06 15:04:45REVIEW #: REVISION 3
 ACTION:
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. THE FOLLOWING ISSUES RELATED TO RATED WALLS AND DUCT
 PENETRATIONS ARE STILL OUTSTANDING:
  
 A) THE DUCT FLOOR PLAN HAS BEEN SPLIT INTO TWO PAGES,
 ONE FOR SUPPLY (M-1A) AND ONE FOR RETURN (M-1B). BOTH
 PAGES ARE MISSING FIRE DAMPERS AT SEVERAL LOCATIONS OF
 DUCT PENETRATIONS OF RATED WALLS. ALSO, SOME FIRE
 DAMPERS ARE SHOWN AT NON-RATED WALL LOCATIONS. SHOW
 COMPLIANCE WITH FBCM 607.2, 607.5 AND 607.8.
 NOTE: ONE SET OF MECHANICAL PLANS HAS BEEN MARKED-UP
 DURING THIS REVIEW TO SHOW RATED WALL LOCATIONS AND
 LOCATIONS OF MISSING DAMPERS AND DAMPERS LOCATED OUT OF
 RATED WALLS.
  
 B) PAGE M-1B SHOWS ALL DAMPERS IN THE RETURN DUCT TO BE
 COMBINATION FIRE/SMOKE DAMPERS. PAGE M-1A SHOWS ONLY
 STANDARD FIRE DAMPERS. WHICH ONE IS CORRECT? PLEASE
 CLARIFY. ALSO, IF FIRE/SMOKE DAMPERS ARE TO BE
 INSTALLED, SMOKE DAMPERS SHALL CLOSE UPON ACTUATION OF
 A LISTED SMOKE DETECTOR OR DETECTORS INSTALLED IN
 ACCORDANCE WITH SECTIONS 907.10 AND 907.11 OF THE
 FLORIDA BUILDING CODE, BUILDING AND ONE OF THE METHODS
 LISTED UNDER FBCM 607.3.2.1, AS APPLICABLE. PLEASE SHOW
 HOW THE SMOKE DAMPERS ARE TO BE ACTUATED IN ACCORDANCE
 WITH THIS SECTION..
  
 C) PAGE M-2 SHOWS SUPPLY DUCT PENETRATIONS AT ROOF
 PROVIDED WITH FIRE/SMOKE DAMPERS. THERE IS NO
 INDICATION ON ARCHITECTURAL PLANS THAT THE ROOF IS A
 FIRE RESISTANCE RATED ASSEMBLY WHICH REQUIRES PROTECTED
 PENETRATIONS. IF DAMPERS ARE REQUIRED, WHY ARE THEY
 ONLY ON THE SUPPLY AND NOT THE RETURN? WHAT TYPE OF
 ASSEMBLY IS BEING PENETRATED? IF DAMPERS ARE TO BE
 INSTALLED, PROVIDE DETAIL SHOWING HOW THESE DAMPERS ARE
 TO BE INSTALLED AT A RATED PENETRATION IN ACCORDANCE
 WITH FBCM 607.6 AND 607.8.
 NOTE: IT APPEARS THAT POSSIBLY THE FIRE/SMOKE DAMPERS
 SHOWN ON THE ROOF ARE SUPPOSED TO BE DUCT SMOKE
 DETECTORS, SINCE THEY ARE ONLY ON THE SUPPLY AND THE
 DUCT SMOKE DETECTORS ARE NOT SHOWN ANYWHERE ON THE
 PLANS. FAN SHUT-DOWN BY SMOKE DETECTOR IS REQUIRED IN
 ACCORDANCE WITH FBCM 606.2.
  
 2. OK
  
 3. OK
  
 4. NO INFORMATION WAS PROVIDED REGARDING THE OUTDOOR
 APPLIANCES, SUCH AS THE ROOFTOP PACKAGE UNITS AND
 EXHAUST FANS, AND THEIR DESIGN RELATED TO WIND
 RESISTANCE. APPLIANCES EXPOSED TO WIND SHALL NOT ONLY
 BE INSTALLED, BUT SHALL ALSO BE DESIGNED TO RESIST WIND
 PRESSURES IN ACCORDANCE WITH FBCM 301.13. PROVIDE
 SUPPORTING DOCUMENTATION FROM THE DESIGNERS OF THESE
 APPLIANCES.
  
 5. OK
  
 6. OK
  
 7. COOLING LOAD CALCULATIONS HAVE NOT BEEN PROVIDED FOR
 THE NEW APPLIANCES BEING INSTALLED. COOLING LOAD
 CALCULATIONS SHALL BE PROVIDED IN ACCORDANCE WITH FBCB
 13-407.1.ABC.1.
  
 8. OK
  
 9. OK
  