2008-06-20 10:34:12** DENIEDREVIEW OF REVISIONS **
  
  
 1) NOTE: PLEASE SUBMIT COMPLETE ELECTRICAL PLANS.
 MECHANICAL PLANS NOW INDICATE ALL NEW ROOF TOP SYSTEMS
 YET NO ELECTRICAL REVISIONS ARE SHOWN FOR DISCONNECTS,
 ROOF TOP SERVICE GFI RECEPTACLES ETC.
 REVISE PANEL SCHEDULES, LOAD CALCULATIONS, CIRCUITING
 ETC.
 SOME SHEETS ARE BEING SUBMITTED AS REVISED YET NO
 REVISIONS ARE SHOWN.
  
 FBC 106.3.5.1.2
 NEC 2005
 440.11, 210.63, 210.8B, 240.4, 310.16 ETC.
  
  
 2) NOTE: PLEASE KNOW EVEN AS VALUE WAS INCREASED THE
 AMOUNT OF INCREASE BASED ON INCREASE OF SCOPE IS LOW.
 THE VALUE IS REQUIRED TO INCLUDE COST OF EQUIPMENT,
 ELECTRICAL, DESIGN, CRANES, ROOFING ETC. PLEASE SUBMIT
 REVISED CONTRACTS TO VERY ALL SCOPE OF WORK FOR PROJECT
 OR ADJUST VALUE. FBC 108.3
 THIS IS REQUIRED EVEN IF ANY EQUIPMENT, ETC IS OWNER
 SUPPLIED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  