| Plan Review Notes For Permit 07071009 |
| Permit Number |
07071009 |
|
| Review Stop |
E |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2008-06-20 10:34:12 | ** DENIEDREVIEW OF REVISIONS ** | | | | | | | | | 1) NOTE: PLEASE SUBMIT COMPLETE ELECTRICAL PLANS. | | | MECHANICAL PLANS NOW INDICATE ALL NEW ROOF TOP SYSTEMS | | | YET NO ELECTRICAL REVISIONS ARE SHOWN FOR DISCONNECTS, | | | ROOF TOP SERVICE GFI RECEPTACLES ETC. | | | REVISE PANEL SCHEDULES, LOAD CALCULATIONS, CIRCUITING | | | ETC. | | | SOME SHEETS ARE BEING SUBMITTED AS REVISED YET NO | | | REVISIONS ARE SHOWN. | | | | | | FBC 106.3.5.1.2 | | | NEC 2005 | | | 440.11, 210.63, 210.8B, 240.4, 310.16 ETC. | | | | | | | | | 2) NOTE: PLEASE KNOW EVEN AS VALUE WAS INCREASED THE | | | AMOUNT OF INCREASE BASED ON INCREASE OF SCOPE IS LOW. | | | THE VALUE IS REQUIRED TO INCLUDE COST OF EQUIPMENT, | | | ELECTRICAL, DESIGN, CRANES, ROOFING ETC. PLEASE SUBMIT | | | REVISED CONTRACTS TO VERY ALL SCOPE OF WORK FOR PROJECT | | | OR ADJUST VALUE. FBC 108.3 | | | THIS IS REQUIRED EVEN IF ANY EQUIPMENT, ETC IS OWNER | | | SUPPLIED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT | | | HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|