Plan Review Notes
Plan Review Notes For Permit 07071009
Permit Number 07071009
Review Stop P
Sequence Number 4
Notes
Date Text
2008-06-10 11:33:23PLUMBING PLAN REVIEW:
 DENIED REVISION:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1. SHEET P-2 ROOF PLAN CD LAYOUT: CLEARLY INDICATE THE
 PIPING MATERIAL BEING USED FOR THE NEW CONDENSATE. PER
 FBC- PLUMBING SECTION 308.3 MATERIAL.
  
 2. SHEET P-2 ROOF PLAN CD LAYOUT: PROVIDE A DETAIL OF
 HOW THE NEW CONDENSATE PIPING WILL BE ANCHORED TO MEET
 140 MPH WIND LOADS. PER FBC-PLUMBING SECTION 308.7
 ANCHORAGE AND FBC- BUILDING CHAPTER 16 SECTION 1609.1.3
 ANCHORAGE AGAINST OVER TURNING, UPLIFT AND SLIDING. .
  
 3. SHEET P-2 CONDENSATE DRAIN DRYWELL DETAIL #4:
 PLEASE CLARIFY HOW THE DRY WELL WITHOUT A COVER
 INSTALLED AND WITH THE TOP OF THE DRY WELL AT GROUND
 LEVEL WILL BE PROTECTED FROM BEING SATURATED DURING
 HEAVY RAIN STORMS, PROTECTED FROM HAVING DIRT OR MULCH
 BEING WASHED INTO IT THEREBY ALLOWING WEEDS TO GROW IN
 IT AND ALSO PROTECTED FROM LAWN MAINTENANCE MATERIALS.
 PER FBC- PLUMBING SECTION 301.1 SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]