| 2008-02-08 20:06:40 | 2008-02-08 20:06:40 |
| | |
| | *** DENIED 4RD REVIEW *** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEWS ARE |
| | STILL IN NEED OF ADDRESSING. SOME OF THESE ITEMS COULD |
| | BE REDLINED HOWEVER NOT ALL. |
| | PLEASE SEE NOTES BELOW. |
| | |
| | ** PLEASE SEE NOTES FROM TWO PREVIOUS REVIEWS WITH |
| | RESPECT TO LIGHTING CONTROLS REQUIRED PER FBC |
| | 13-415.1.ABC.1.1 AND .1.2. |
| | THE PLANS WERE REVISED TO INDICATE THAT THE DEVICES IN |
| | EACH ROOM ARE NOW A DEVICE WHICH CONTAINS A TIMER FOR A |
| | MAXIMUM OF FOUR HOURS AND IS NOT PART OF ANY LIGHTING |
| | CONTROL SYSTEM. |
| | PLEASE SEE THE TS-400 IS A DEVICE WITH A MAXIMUM TIME |
| | OF 12HRS AS STATED ON THE WATTSTOPPER WEBSITE. PLEASE |
| | SEE 13-415.1.ABC.1.2 WHICH REQUIRES SPACES SUCH AS |
| | CLASSROOMS, EMPLOYEE LUNCH/BREAK ROOMS AND CONFERENCE |
| | ROOMS TO CONTAIN DEVICES WHICH DOES NOT PERMIT THE |
| | LIGHTING TO REMAIN ON FOR MORE THAN 30MINS AFTER THE |
| | LAST OCCUPANT HAS VACATED THE ROOM. THE TIMER AS NOTED |
| | DOES NOT MEET THE 30MINS FOR THESE ROOMS. THESE FEW |
| | ROOMS COULD BE RED-LINED HOWEVER PLEASE STILL SEE |
| | 13-415.1.ABC.1.1 WHICH NO LIGHTING CONTROLS COULD BE |
| | LOCATED FOR THE COMMON HALLWAY AREAS. |
| | THE FRONT LOBBY ENTRANCE AREAS DO SHOW SOME OF THESE SA |
| | DEVICES WHICH ARE NOTED AS 4HR TIMERS PERNOTE ON E-4 |
| | HOWEVER THE OTHER AREAS DO NOT SHOW ANYTHING BUT |
| | STANDARD S3 AND S4 FOR THREE-WAY AND FOUR-WAY |
| | SWITCHES. |
| | ** PLEASE SEE THE CODE SECTIONS GIVEN AND ADJUST |
| | PLANS. |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO |
| | LIGHTING POWER CALCULATIONS. PLEASE SEE 13-415.2 PLEASE |
| | SEE THE TABLE WHICH HAS BEEN ADJUSTED. PLEASE SEE THE |
| | FIXTURE COUNT FOR TYPE B SHOWS 45, YET PLANS CONTAIN |
| | 47. |
| | PLEASE SEE THE MAIN CONCERN IS THE TYPE A FIXTURES. |
| | SHOWS 3-28W T5 WHICH BY THE FIXTURE LEGEND AND THE |
| | CALCULATION TABLES INDICATES THESE AS 75W FIXTURES? |
| | THIS IS UNCLEAR HOW THIS IS POSSIBLE. A SEARCH BASED ON |
| | THE METALUX FIXTURES ON COOPER LIGHTING WEBSITE DOES |
| | NOT COORDINATE WITH THE SAME TYPE OF AC FIXTURES AS |
| | NOTED. PLEASE SEE MANY FIXTURES INDICATE FIXTURES WITH |
| | BALLAST WITH AVAILABLE *POWER FACTORS* WHICH WOULD |
| | ADJUST ACTUAL USE INSTEAD OF BEING BASED ON THE BULB |
| | WATTAGE. |
| | COULD NOT LOCATE THE FIXTURE, BALLAST, ETC WHICH IS THE |
| | TYPE AS LISTED ON LEGEND. PLEASE SUBMIT THE |
| | MANUFACTURES SPEC/CUT SHEET OR E-MAIL THE SPECS, OR |
| | WEB-SITE LINK WHICH SHOWS THESE FIXTURES. THE SITE |
| | SPECS FOR THIS TYPE METALUX 2AC AS LISTED ARE ATTACHED |
| | TO NOTES WHICH INDICATE A 2 LAMP FIXTURE. |
| | PLEASE SEE ATTACHED SHEETS FOR THE TROFFER RECESSED |
| | LIGHTS AS STATED ON LEGEND. |
| | RESPONSE LETTER MENTIONS FIXTURES CONTAIN A HIGH-POWER |
| | FACTOR WHICH IS FINE HOWEVER COULD NOT LOCATE THE SAME |
| | POWER FACTOR ON THIS FIXTURE WHICH COORDINATES WITH THE |
| | 75WATTS. |
| | |
| | |
| | ** AS STATED ON PREVIOUS REVIEW, PLEASE GO OVER ALL |
| | FIXTURES ON PLANS, FIGURE WATTS PER SQUARE FEET BASED |
| | ON THE NUMBER OF FIXTURES AND THE RATING OF FIXTURE |
| | OUTPUT. |
| | |
| | IF THERE ARE ANY QUESTIONS ON THE ABOVE NOTED ITEMS, |
| | PLEASE CONTACT THIS OFFICE AT THE CONTACT INFORMATION |
| | BELOW. |
| | |