2008-01-19 13:52:40REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 ALL PREVIOUS REVIEW COMMENTS HAVE BEEN ADDRESSED WITH
 THE EXCEPTION OF THE FOLLOWING:
  
 M-1: NOTE FOR MOTORIZED DAMPERS, THE OUTSIDE AIR
 DAMPERS ARE TO BE CLOSED WHENEVER BUILDING IS IN
 UNOCCUPIED MODE, REGARDLESS OF WHETHER AHU'S ARE
 RUNNING. CORRECT NOTE TO SHOW DAMPERS CLOSED DURING
 UNOCCUPIED MODE. FBC 13-409.1.ABC.3.3
  
 M-2: FRESH AIR SCHEDULE FOR AHU-4 SHOWS 1,000 CFM OF
 OUTSIDE AIR REQUIRED, BUT THE DESIGN CFM ONLY CALLS FOR
 30 CFM. PLEASE CORRECT AND RESUBMIT. FBC, M 403.3.
  