Plan Review Notes
Plan Review Notes For Permit 07071009
Permit Number 07071009
Review Stop E
Sequence Number 3
Notes
Date Text
2007-12-25 12:07:092007-12-25 12:07:09
  
 ** DENIED 3RD REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
  
 1) NOTE: PLEASE SEE NOTE #2 FROM PREVIOUS REVIEW. PLANS
 INDICATE A TIMER OVER RIDE DEVICE WHICH LENDS TO SOME
 SORT OF SYSTEM BEING INSTALLED HOWEVER THE PLANS DO NOT
 PROVIDE ANY SYSTEM.A TIMER OVER RIDE IS FOR OVER
 RIDING SOME SORT OF LIGHTING CONTROL SYSTEM.
 NO DETAILS FOR ANY TYPE OF LIGHTING CONTROL PANEL WAS
 SUBMITTED, NO PANELS, NO SCHEDULING ETC.
 PLEASE COMPLETE AND SUBMIT.
  
 2) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE
 CALCULATIONS ARE NOW SUBMITTED. PLEASE SEE THE METHOD
 IS NOT STATED HOWEVER IT IS BEING ASSUMED THIS IS FROM
 TABLE *C*.
 PLEASE SEE THE CALCULATIONS NEED TO BE EXPANDED UPON.
 WHAT SQ FT IS BEING FIGURED AND FOR WHAT SPACE? DOES
 THIS INCLUDE ONLY NEW AREA WHERE WORK IS BEING DONE?
 MAY NOT USE THE EXISTING AREAS (SQ FT) NOT BEING DONE
 WITH NEW LIGHTING.
 PLEASE ALSO SEE THE WATTAGE PER FIXTURE WHICH IS
 REQUIRED TO BE USED SHALL BE BASED ON THE MAXIMUM
 FIXTURE WATTAGE FOR INCANDESCENT AND MAXIMUM VALUE FOR
 FIXTURES WITH PERMANENTLY INSTALLED BALLAST AND THEIR
 LISTED OUTPUT. THIS CAN BE FOUND IN 13-415.2.ABC.1.3
 (1) (2)
 BASED ON THE FIXTURE LEGEND AND WATTAGE PER FIXTURE
 SHOWN, THE TOTAL ON TABLE AS SHOWN IS LOWER THAN AMOUNT
 FIGURED BY THIS OFFICE.
 PLEASE GO OVER ALL FIXTURES AND EXPAND ON THE SQ FT
 USE. PLEASE ALSO BE SURE TO PLACE INFORMATION FOR ANY
 CHANGES IN BALLAST VA OUTPUTS.
 PLEASE SEE NOTE ON TABLE MENTIONS TOTAL FIXTURE
 *COMBUSTION* THIS SEEMS TO BE A MISPRINT FOR
 *CONSUMPTION*.
  
 3) NOTE: NEW NOTE* PLEASE SEE 13-413.1.ABC.2.1 AND .2.2
 AND PLACE NOTE SON PLANS ACCORDINGLY. THIS WAS
 CONFIRMED WITH THE FLORIDA BUILDING COMMISSION SINCE
 THE LAST REVIEW AND NOTES ARE REQUIRED ON PLANS.
  
 ** CODES REFLECTED ON SHEET E-8 PART 3 ARE NOT FROM
 CURRENT CODE. (99 NEC) THIS CAN BE REDLINED WITH OUT
 PRINTING NEW SHEET.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  