| 2007-12-06 07:22:06 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS |
| | TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED 2ND TIME: |
| | |
| | *****PREVIOUS REVIEW COMMENTS***** |
| | |
| | 1. PLEASE CORRECT THE TITLE BLOCK INDICATING THE WRONG |
| | ARCHITECTURAL FIRM LICENSE NUMBER FOR GAMBACH |
| | ARCHITECTS INC. PER FAC 61G1-16.004 AND FS 481.219 ON |
| | THE RESUBMITTAL. |
| | **NOTE: COMMENT NOT ADDRESSED. PLEASE SEE ATTACHED DBPR |
| | PRINT OUT WITH CORRECT FIRM LICENSE NUMBER TO THESE |
| | PLUMBING COMMENTS. PLEASE SEE ALL SHEETS NEED TO COMPLY |
| | ON RESUBMITTAL. |
| | |
| | 2. OK, COMMENT ADDRESSED. |
| | |
| | *****THE FOLLOWING ARE NEW COMMENTS***** |
| | |
| | 3. SHEET A-6 AND P-1 REST AREA ARE INDICATING AN ADDED |
| | SINK THAT IS NOT CLEARLY IDENTIFIED. PLEASE CLEARLY |
| | IDENTIFY THIS SINK ON THE RESUBMITTAL AND ADD THE |
| | REQUIRED SANITARY AND WATER TO THE RISER DIAGRAMS, |
| | DETAILED PLUMBING LAYOUT, AND PLUMBING FIXTURE SCHEDULE |
| | ON SHEET P-1. PER 106.3.5.1.3, PLUMBING. |
| | |
| | 4. NOTE: THE ADDED SINK IN REST AREA SHALL BE |
| | ACCESSIBLE PER CHAPTER 11, THE FOLLOWING SECTIONS. |
| | |
| | **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE |
| | FOLLOWING INFORMATION) |
| | 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR |
| | COUNTER. |
| | 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE, |
| | AND 19" DEEP.(NO CABINET DOORS OR BASE) |
| | 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP. |
| | 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR |
| | SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE |
| | SINK.(NO CABINET DOORS OR BASE) |
| | 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO |
| | PROTECT AGAINST CONTACT. |
| | 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR |
| | ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS. |
| | |
| | END OF COMMENTS: |
| | |