| 2007-11-24 09:12:07 | REVIEW #: 2ND |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. THIS COMMENT WAS NOT ADDRESSED. PROVIDE A LEGEND ON |
| | PLANS SHOWING THE MEANINGS OF ABBREVIATIONS AND SYMBOLS |
| | ON PLANS. FBC 106.1.1. |
| | |
| | 2. LETTER FROM ENGINEER REGARDING EXISTING EQUIPMENT IS |
| | NOTED. ENERGY CALCULATIONS ARE NOT REQUIRED. |
| | NOTE: ALL NEW COMPONENTS, SUCH AS DUCTWORK, ARE SUBJECT |
| | TO THE MINIMUM PRESCRIPTIVE REQUIREMENTS OF FBC CHAPTER |
| | 13 IN ACCORDANCE WITH FBC, EB 611.1 AND FBC |
| | 13-400.0.C.4. SHOW ALL NEWLY INSTALLED COMPONENTS IN |
| | SUFFICIENT DETAIL TO DEMONSTRATE COMPLIANCE WITH FBC |
| | CH. 13. |
| | |
| | 3. THIS COMMENT WAS NOT ADDRESSED. SEE PREVIOUS COMMENT |
| | FOR RELEVANT CODE SECTIONS AND REQUIREMENTS. |
| | |
| | 4. OK. REVIEW COMMENTS RELATED TO FLOOR PLANS WILL BE |
| | AT THE END OF COMMENTS 1 THROUGH 10. |
| | |
| | 5. OK. REVIEW COMMENTS RELATED TO FLOOR PLANS WILL BE |
| | AT THE END OF COMMENTS 1 THROUGH 10. |
| | |
| | 6. BASED ON THE ATTACHED LETTER FROM THE ENGINEER, |
| | THERE IS NO NEW A/C EQUIPMENT BEING INSTALLED. |
| | THEREFORE, DETAILS FOR NEWLY INSTALLED EQUIPMENT ON M-2 |
| | ARE NOT APPLICABLE AND SHOULD BE REMOVED, UNLESS |
| | EXISTING EQUIPMENT IS BEING RETROFITTED TO MATCH THE |
| | INSTALLATION METHODS SHOWN IN THE DETAILS. FBC, EB |
| | 609.2. |
| | |
| | 7. SAME AS COMMENT #6 ABOVE. |
| | |
| | 8. SAME AS COMMENT #6 ABOVE. |
| | |
| | 9. THIS COMMENT WAS NOT ADDRESSED. |
| | |
| | 10. THIS IS A MINIMUM PRESCRIPTIVE REQUIREMENT OF FBC |
| | CHAPTER 13 AND SHALL BE IN COMPLIANCE PER FBC, EB |
| | 611.1. ALSO, PROVIDE SHUTOFF DAMPER CONTROLS IN |
| | ACCORDANCE WITH FBC 13-409.1.ABC.3.3 AND FBC, EB |
| | 611.1. |
| | |
| | NEW COMMENTS: THE FOLLOWING NEW COMMENTS ARE THE RESULT |
| | OF INFORMATION WHICH WAS MISSING FROM PLANS DURING |
| | FIRST REVIEW. |
| | |
| | A. M-1: BASED ON THE LOCATIONS OF RATED WALL ASSEMBLIES |
| | AS SHOWN ON A-6, THERE ARE SEVERAL LOCATIONS WHERE |
| | DUCTS ARE SHOWN PENETRATING RATED WALLS. SHOW OPENING |
| | PROTECTIVES AT THESE DUCT PENETRATIONS AS REQUIRED BY |
| | FBC, M 607.5. ONE SET OF PLANS HAS BEEN MARKED TO SHOW |
| | MANY (BUT POSSIBLY NOT ALL) LOCATIONS. |
| | |
| | B. PLEASE PROVIDE A WRITTEN NARRATIVE OR RESPONSE TO |
| | PLAN REVIEW COMMENTS AS THIS WILL SPEED THE REVIEW |
| | PROCESS AND ASSIST IN OBTAINING A PERMIT. |
| | |