| 2007-12-13 16:08:20 | *****DENIED***** |
| | |
| | THE FOLLOWING COMMENTS (OF 10) FROM THE PREVIOUS REVIEW |
| | STILL NEED TO BE ADDRESSED: |
| | |
| | 02.DOORS THAT LEAD FROM SPECIFIC OFFICES THAT ARE |
| | MARKED AS EXITS, SHALL NOT BE CREDITED AS EXITS.THERE |
| | WOULD NOT BE CLEAR UNOBSTRUCTED TRAVEL AS IT APPLIES TO |
| | REQUIRED MEANS OF EGRESS. |
| | |
| | 04.SPECIFY THE MINIMUM INTERIOR FINISH MATERIALS FOR |
| | THE WALLS AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR |
| | CLASS C. |
| | |
| | 05.PLEASE SHOW THE LOCATION OF THE FIRE ALARM CONTROL |
| | PANEL ON THE FIRE ALARM LAYOUT SHEET. |
| | |
| | 07.SMOKE DUCT DETECTORS SHALL INITIATE A GENERAL FIRE |
| | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.ON SHEET |
| | E-6, AMEND FIRE ALARM SEQUENCE OF OPERATION. |
| | |
| | 09.FIRE ALARM NOTES PART 3 (SHEET E-6) REFERENCES |
| | FIRE SPRINKLER EQUIPMENT.IF THIS BUILDING IS |
| | PROTECTED BY AUTOMATIC FIRE SPRINKLER SYSTEM, PLEASE |
| | ADVISE AND INCLUDE SPRINKLER LAYOUT.IF NOT, PLEASE |
| | REMOVE ALL REFERENCES ON PLANS. |
| | |
| | 10.PLEASE ILLUSTRATE THE LOCATION OF THE 2A-10BC |
| | RATED FIRE EXTINGUISHERS THAT SHALL BE MOUNTED AT |
| | DISTANCES NOT TO EXCEED 75' TRAVEL DISTANCE. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS |
| | ADDRESSED |
| | |
| | |