Plan Review Notes
Plan Review Notes For Permit 07071009
Permit Number 07071009
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-12-13 16:08:20*****DENIED*****
  
 THE FOLLOWING COMMENTS (OF 10) FROM THE PREVIOUS REVIEW
 STILL NEED TO BE ADDRESSED:
  
 02.DOORS THAT LEAD FROM SPECIFIC OFFICES THAT ARE
 MARKED AS EXITS, SHALL NOT BE CREDITED AS EXITS.THERE
 WOULD NOT BE CLEAR UNOBSTRUCTED TRAVEL AS IT APPLIES TO
 REQUIRED MEANS OF EGRESS.
  
 04.SPECIFY THE MINIMUM INTERIOR FINISH MATERIALS FOR
 THE WALLS AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR
 CLASS C.
  
 05.PLEASE SHOW THE LOCATION OF THE FIRE ALARM CONTROL
 PANEL ON THE FIRE ALARM LAYOUT SHEET.
  
 07.SMOKE DUCT DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.ON SHEET
 E-6, AMEND FIRE ALARM SEQUENCE OF OPERATION.
  
 09.FIRE ALARM NOTES PART 3 (SHEET E-6) REFERENCES
 FIRE SPRINKLER EQUIPMENT.IF THIS BUILDING IS
 PROTECTED BY AUTOMATIC FIRE SPRINKLER SYSTEM, PLEASE
 ADVISE AND INCLUDE SPRINKLER LAYOUT.IF NOT, PLEASE
 REMOVE ALL REFERENCES ON PLANS.
  
 10.PLEASE ILLUSTRATE THE LOCATION OF THE 2A-10BC
 RATED FIRE EXTINGUISHERS THAT SHALL BE MOUNTED AT
 DISTANCES NOT TO EXCEED 75' TRAVEL DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  