| Date |
Text |
| 2007-11-08 16:49:29 | ** DENIED 2ND REVIEW ** |
| | |
| | |
| | ** PLEASE SEE THERE ARE SOME COMMENTS FROM PREVIOUS |
| | REVIEW WHICH ARE IN NEED OF ADDRESSING ALONG WITH NEW |
| | COMMENTS AS THERE ARE ITEMS NOW ON PLANS WHICH HAVE NEW |
| | COMMENTS. |
| | |
| | 1) NOTE: PLEASE SEE THE INFORMATION ON THE TITLE BLOCKS |
| | FOR ARCHITECTURAL FIRM DOES NOT CORRELATE AND |
| | INFORMATION COULD NOT BE CONFIRMED WITH THE STATE |
| | DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION. |
| | PLEASE SEE THE TITLE BLOCKS ON A SHEETS CONTAINS A |
| | DIFFERENT LICENSE NUMBER THAN THE NUMBER LISTED ON |
| | E-SHEETS FOR ARCHITECTURAL FIRM. |
| | PLEASE SEE ATTACHED PRINT OUT FROM STATE WITH NUMBER AS |
| | LISTED. |
| | PLEASE SE FAC61G1-16.004, FS 481.219 |
| | ** REQUIRED FOR ALL SHEETS AND FOR ALL TRADES WHETHER |
| | OR NOT COMMENT IS MADE BY OTHER TRADES. |
| | |
| | 2) NOTE: PLEASE SEE MISSING LIGHTING CONTROLS PER FBC |
| | CHAPTER 13. PREVIOUS REVIEW WENT OVER THE SCOPE AND |
| | THAT NEW LIGHTING AND DEVICES WAS UNCLEAR. AS PLANS NOW |
| | INDICATE THESE ITEMS AS NEW, THE NEW DEVICES SHALL |
| | COMPLY WITH 13-415.1.ABC.1.1, AND .1.2. |
| | |
| | 3) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.2, 13-101. |
| | PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS FOR |
| | ROOMS IN WHICH NEW LIGHTING IS BEING INSTALLED. |
| | |
| | 4) NOTE: PLEASE NFPA-101 708 AND 7.9 AND THE MINIMUM |
| | LIGHTING LEVELS FOR EGRESS PATHS, EXIT ACCESS |
| | CORRIDORS, EXIT CORRIDORS ETC ARE REQUIRED. |
| | PLEASE INDICATE THE LIGHTING FIXTURES, CIRCUITING PER |
| | 700.12F COMPLETE PHOTO-METRIC PATHS. |
| | FAC 61G15-33.004 |
| | FBC 106.1.2. |
| | |
| | 5) NOTE: PLEASE SEE THE PLANS WILL BE ROUTED TO |
| | ADDRESSING AS THIS SPACE SEEMS TO BE PART OF A LARGER |
| | BUILDING IN WHICH THIS SPACE WOULD HAVE A UNIT/SUITE.. |
| | IF THIS IS A SUITE OR UNIT PLEASE INDICATE THE |
| | SUITE/UNIT ON PLANS. |
| | ** PLEASE SEE COMMENTS FROM OTHER REVIEWERS FOR THIS. |
| | |
| | 6) NOTE: PLEASE KNOW THAT A RESPONSE LETTER EVEN THOUGH |
| | NOT REQUIRED DOES HELP THE REVIEW PROCESS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |