Plan Review Notes
Plan Review Notes For Permit 07071009
Permit Number 07071009
Review Stop E
Sequence Number 2
Notes
Date Text
2007-11-08 16:49:29** DENIED 2ND REVIEW **
  
  
 ** PLEASE SEE THERE ARE SOME COMMENTS FROM PREVIOUS
 REVIEW WHICH ARE IN NEED OF ADDRESSING ALONG WITH NEW
 COMMENTS AS THERE ARE ITEMS NOW ON PLANS WHICH HAVE NEW
 COMMENTS.
  
 1) NOTE: PLEASE SEE THE INFORMATION ON THE TITLE BLOCKS
 FOR ARCHITECTURAL FIRM DOES NOT CORRELATE AND
 INFORMATION COULD NOT BE CONFIRMED WITH THE STATE
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION.
 PLEASE SEE THE TITLE BLOCKS ON A SHEETS CONTAINS A
 DIFFERENT LICENSE NUMBER THAN THE NUMBER LISTED ON
 E-SHEETS FOR ARCHITECTURAL FIRM.
 PLEASE SEE ATTACHED PRINT OUT FROM STATE WITH NUMBER AS
 LISTED.
 PLEASE SE FAC61G1-16.004, FS 481.219
 ** REQUIRED FOR ALL SHEETS AND FOR ALL TRADES WHETHER
 OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 2) NOTE: PLEASE SEE MISSING LIGHTING CONTROLS PER FBC
 CHAPTER 13. PREVIOUS REVIEW WENT OVER THE SCOPE AND
 THAT NEW LIGHTING AND DEVICES WAS UNCLEAR. AS PLANS NOW
 INDICATE THESE ITEMS AS NEW, THE NEW DEVICES SHALL
 COMPLY WITH 13-415.1.ABC.1.1, AND .1.2.
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.2, 13-101.
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS FOR
 ROOMS IN WHICH NEW LIGHTING IS BEING INSTALLED.
  
 4) NOTE: PLEASE NFPA-101 708 AND 7.9 AND THE MINIMUM
 LIGHTING LEVELS FOR EGRESS PATHS, EXIT ACCESS
 CORRIDORS, EXIT CORRIDORS ETC ARE REQUIRED.
 PLEASE INDICATE THE LIGHTING FIXTURES, CIRCUITING PER
 700.12F COMPLETE PHOTO-METRIC PATHS.
 FAC 61G15-33.004
 FBC 106.1.2.
  
 5) NOTE: PLEASE SEE THE PLANS WILL BE ROUTED TO
 ADDRESSING AS THIS SPACE SEEMS TO BE PART OF A LARGER
 BUILDING IN WHICH THIS SPACE WOULD HAVE A UNIT/SUITE..
 IF THIS IS A SUITE OR UNIT PLEASE INDICATE THE
 SUITE/UNIT ON PLANS.
 ** PLEASE SEE COMMENTS FROM OTHER REVIEWERS FOR THIS.
  
 6) NOTE: PLEASE KNOW THAT A RESPONSE LETTER EVEN THOUGH
 NOT REQUIRED DOES HELP THE REVIEW PROCESS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]