2009-06-01 16:03:48REVISED M-3 DENIED:
  
 NOTE #13 HAS BEEN REMOVED FROM PLANS. THIS NOTE CALLED
 FOR MOTORIZED DAMPERS ON RTU OA INTAKES TO CLOSE WHEN
 BUILDING WAS IN UNOCCUPIED MODE. WITHOUT THIS THERE IS
 NO COMPLIANCE WITH FBC-B SECTION 13-409.1.ABC.3.3 FOR
 SHUTOFF DAMPER CONTROLS. ANY REVISION TO PLANS MUST
 STILL SHOW COMPLIANCE WITH THIS SECTION. PLEASE SHOW ON
 PLANS HOW AUTOMATIC SHUTOFF DAMPER CONTROLS ARE TO BE
 PROVIDED. THE DESIGNER'S ASSERTION THAT THE DAMPERS ARE
 NOT REQUIRED IS NOT ACCEPTED AS A VALID INTERPRETATION
 OF THE INTENT OF THIS CODE SECTION. MOTORIZED DAMPERS
 SHALL BE INSTALLED AND DESIGNED TO CLOSE WHENEVER THE
 BUILDING IS IN UNOCCUPIED MODE.
  
 ALSO, SEVERAL SECTIONS OF PAGE M-3 ARE OF POOR QUALITY
 AND NOT LEGIBLE. PLEASE SUBMIT PLANS WHICH ARE CLEAR
 AND LEGIBLE IN ACCORDANCE WITH FBC-B SECTION 106.1.1.
  