| Plan Review Notes For Permit 07071009 |
| Permit Number |
07071009 |
|
| Review Stop |
M |
| Sequence Number |
11 |
|
| Notes |
| Date |
Text |
| 2009-06-01 16:03:48 | REVISED M-3 DENIED: | | | | | | NOTE #13 HAS BEEN REMOVED FROM PLANS. THIS NOTE CALLED | | | FOR MOTORIZED DAMPERS ON RTU OA INTAKES TO CLOSE WHEN | | | BUILDING WAS IN UNOCCUPIED MODE. WITHOUT THIS THERE IS | | | NO COMPLIANCE WITH FBC-B SECTION 13-409.1.ABC.3.3 FOR | | | SHUTOFF DAMPER CONTROLS. ANY REVISION TO PLANS MUST | | | STILL SHOW COMPLIANCE WITH THIS SECTION. PLEASE SHOW ON | | | PLANS HOW AUTOMATIC SHUTOFF DAMPER CONTROLS ARE TO BE | | | PROVIDED. THE DESIGNER'S ASSERTION THAT THE DAMPERS ARE | | | NOT REQUIRED IS NOT ACCEPTED AS A VALID INTERPRETATION | | | OF THE INTENT OF THIS CODE SECTION. MOTORIZED DAMPERS | | | SHALL BE INSTALLED AND DESIGNED TO CLOSE WHENEVER THE | | | BUILDING IS IN UNOCCUPIED MODE. | | | | | | ALSO, SEVERAL SECTIONS OF PAGE M-3 ARE OF POOR QUALITY | | | AND NOT LEGIBLE. PLEASE SUBMIT PLANS WHICH ARE CLEAR | | | AND LEGIBLE IN ACCORDANCE WITH FBC-B SECTION 106.1.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|