| 2009-02-15 16:06:34 | REVISED M-3 DENIED: | | | | | | NOTE #13 HAS BEEN REMOVED FROM PLANS. THIS NOTE CALLED | | | FOR MOTORIZED DAMPERS ON RTU OA INTAKES TO CLOSE WHEN | | | BUILDING WAS IN UNOCCUPIED MODE. WITHOUT THIS THERE IS | | | NO COMPLIANCE WITH FBC-B SECTION 13-409.1.ABC.3.3 FOR | | | SHUTOFF DAMPER CONTROLS. ANY REVISION TO PLANS MUST | | | STILL SHOW COMPLIANCE WITH THIS SECTION. PLEASE SHOW ON | | | PLANS HOW AUTOMATIC SHUTOFF DAMPER CONTROLS ARE TO BE | | | PROVIDED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|