2009-02-15 16:06:34REVISED M-3 DENIED:
  
 NOTE #13 HAS BEEN REMOVED FROM PLANS. THIS NOTE CALLED
 FOR MOTORIZED DAMPERS ON RTU OA INTAKES TO CLOSE WHEN
 BUILDING WAS IN UNOCCUPIED MODE. WITHOUT THIS THERE IS
 NO COMPLIANCE WITH FBC-B SECTION 13-409.1.ABC.3.3 FOR
 SHUTOFF DAMPER CONTROLS. ANY REVISION TO PLANS MUST
 STILL SHOW COMPLIANCE WITH THIS SECTION. PLEASE SHOW ON
 PLANS HOW AUTOMATIC SHUTOFF DAMPER CONTROLS ARE TO BE
 PROVIDED.
  