| 2007-08-14 19:53:15 | ------------------DENIED------------------- |
| | |
| | FBC 2004 CODE FAMILY WITH 2005 AND 2006 REVISIONS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PROVIDE A LEGEND SHOWING THE MEANINGS OF |
| | ABBREVIATIONS AND SYMBOLS ON MECHANICAL FLOOR PLANS. |
| | FBC 106.1.1. |
| | |
| | 2. PROVIDE EQUIPMENT SCHEDULE SHOWING MODEL, SIZE, |
| | RATINGS, EFFICIENCY AND ELECTRICAL REQUIREMENTS. FBC |
| | 106.3.5.1.4. ALTERATIONS SUBJECT TO THIS CHAPTER SHALL |
| | COMPLY WITH THE REQUIREMENTS OF CHAPTER 13 OF THE |
| | FLORIDA BUILDING CODE, BUILDING. FBC, EB 611.1 |
| | |
| | 3. PROVIDE OUTDOOR AIR CALCULATIONS BASED ON FBC,M |
| | TABLE 403.3. INCLUDE OCCUPANCY CLASSIFICATION, OCCUPANT |
| | LOAD, OUTDOOR AIR RATE, OUTDOOR AIR REQUIRED AND |
| | OUTDOOR AIR PROVIDED. ALL RECONFIGURED SPACES INTENDED |
| | FOR OCCUPANCY AND ALL SPACES CONVERTED TO HABITABLE OR |
| | OCCUPIABLE SPACE IN ANY WORK AREA SHALL BE PROVIDED |
| | WITH NATURAL OR MECHANICAL VENTILATION OR EXHAUST IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL. |
| | FBC, EB 609.2 |
| | |
| | 4. PG A6 AND A7, PRINTING O PLANS IS OF POOR QUALITY |
| | MAKING IT DIFICULT TO DIFFERENTIATE BETWEEN WALL TYPES. |
| | ALSO, THERE IS NO WALL LEGEND ON PG A7, YET THERE ARE |
| | WALL TYPES WHICH DIFFER FROM THE LEGEND ON A6. PLEASE |
| | CLARIFY AS THE LOCATION OF RATED WALLS WILL IMPACT |
| | MECHANICAL PLAN REVIEW. |
| | |
| | 5. SEVERAL AREAS ON PG A6 ARE MARKED AS "NOT PART OF |
| | THIS PERMIT" BUT THOSE AREAS ARE SHOWN ON M-1 AS PART |
| | OF THE SCOPE OF WORK. THE ACTUAL SCOPE OF WORK RELATED |
| | TO MECHANICAL CAN NOT BE DETERMINED AND IS UNCLEAR |
| | BASED ON THE INFORMATION PROVIDED IN THESE PLANS. FLOOR |
| | PLAN CAN NOT BE REVIEWED AT THIS TIME. |
| | |
| | 6. M-2: DETAIL FOR NEW EQUIPMENT ON ROOF, PLEASE |
| | PROVIDE A ROOF PLAN SHOWING THE LAYOUT OF EQUIPMENT, |
| | LOCATION OF EXHAUST AND INTAKE OPENINGS. ALSO, CU STAND |
| | NOA AND INSTALLATION INSTRUCTIONS WERE NOT INCLUDED IN |
| | THIS SUBMITTAL. PLEASE PROVIDE THEM ALONG WITH ALL |
| | REQUIRED SUPPORTING DOCUMENTATION. |
| | |
| | 7. M-2: STRTAPS ON CU'S FOR WIND LOADS SHALL NOT |
| | INTERFERE WITH SERVICE ACCESS OF EQUIPMENT PER FBC,M |
| | 306.1. |
| | |
| | 8. NOTES ON EQUIPMENT REFERENCE DIFFERENT REGIONS AND |
| | DIFFERENT WIND LOAD REQUIREMENTS. THIS PROJECT IS |
| | LOCATED IN THE CITY OF WEST PALM BEACH AND AS SUCH, IS |
| | IN THE 140 MPH WIND ZONE. SHOW ALL OUTDOOR ATTACHMENTS |
| | TO BE DESIGNED FOR THESE WIND LOADS PER FBC,M 301.13 |
| | AND FBC CH.16. |
| | |
| | 9. SHOW MEANS AND LOCATION OF ALL CONDENSATE DISPOSAL |
| | PER FBC,M 307.2.1 THROUGH 307.2.5. |
| | |
| | 10. PROVIDE AN AIR BALANCE SCHEDULE FOR THE BUILDING |
| | SHOWING OVERALL BUILDING PRESSURIZATION. MECHANICAL |
| | SYSTEMS SHALL BE DESIGNED TO ASSURE THAT BUILDINGS ARE |
| | PRESSURIZED WITH RESPECT TO OUTDOORS. FBC |
| | 13-409.1.ABC.2. ALTERATIONS SUBJECT TO THIS CHAPTER |
| | SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTER 13 OF THE |
| | FLORIDA BUILDING CODE, BUILDING. FBC, EB 611.1 |
| | |