| 2007-09-07 10:53:23 | ***DENIED*** |
| | |
| | 1) SITE PLAN IS DIFFICULT TO READ. |
| | |
| | 2) DOORS THAT LEAD FROM SPECIFIC OFFICES THAT ARE MAKED |
| | AS EXITS, SHALL NOT BE CREDITED AS EXITS. THERE WOULD |
| | NOT BE CLEAR UNOBSTRUCTED TRAVEL AS IT APPLIES TO |
| | REQUIRED MEANS OF EGRESS. |
| | |
| | 3) FIRE RATED DOORS SHALL BE PROVIDED WITH UL LISTED |
| | CLOSERS. PLEASE INDICATE IN DOOR SCHEDULE. |
| | |
| | 4) PLEASE PROVIDE MINIMUM INTERIOR FINISH |
| | CLASSIFICATION FOR WALLS AND CEILING. |
| | |
| | 5) PLEASE SHOW THE LOCATION OF THE FIRE ALARM CONTROL |
| | PANEL ON THE FIRE ALARM LAYOUT SHEET. |
| | |
| | 6) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE |
| | ALARM REMODEL. |
| | |
| | 7) IN ACCORDANCE WITH LOCAL REQUIREMENTS, DUCT SMOKE |
| | DETECTORS IN ADDITION TO FAN SHUT DOWN, SHALL INITIATE |
| | A GENERAL FIRE ALARM. (FA SEQUENCE OF OPERATION) |
| | |
| | 8) FIRE NOTES ON E-6 REFERENCE THE INCORRECT EDITION OF |
| | NFPA 101. SHOULD READ 2003 EDITION. |
| | |
| | 9) FIRE ALARM NOTES PART 3 REFERENCE FIRE SPRINKLER |
| | EQUIPMENT. IF THIS BUILDING IS PROTECTED BY AUTOMATIC |
| | FIRE SPRINKLER SYSTEM, PLEASE ADVISE AND INCLUDE |
| | SPRINKLER LAY OUT. IF NOT, PLEASE REMOVE ALL REFERENCES |
| | ON PLANS. |
| | |
| | 10) PLEASE ILLUSTRATE THE LOCATION OF 2A-10B,C RATED |
| | FIRE EXTINGUISHERS THAT SHALL BE MOUNTED AT DISTANCES |
| | NOT TO EXCEED 75' TRAVEL DISTANCE. |
| | |
| | |
| | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL |
| | FIRE PLAN REVIEW |
| | FIRE PREVENTION (561) 804-4756 |