| 2007-08-14 08:47:36 | |
| | *** DENIED *** |
| | |
| | *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET |
| | SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE |
| | REVIEWED AT THIS TIME. |
| | |
| | ** PLEASE SEE AN INITIAL REVIEW WAS DONE UNDER 07060876 |
| | WHICH IS NOW INTERIOR DEMO ONLY PERMIT. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE THE |
| | CODES TO BE STATED ON PLANS. PLEASE SEE THE FOLLOWING |
| | ARE REQUIRED FOR ELECTRICAL AND OTHERS WILL BE REQUIRED |
| | FOR OTHER TRADES. PLEASE KNOW AS OF DECEMBER 8TH, 2006 |
| | THE STATE ADOPTED THE 2006 REVISIONS TO THE 2004 FBC |
| | AND THE 2005 NFPA-70. PLEASE LIST THE FOLLOWING 2004 |
| | FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | ** PLEASE SEE THERE ARE SEVERAL CODES LISTED ON PLANS |
| | WHICH NEED TO BE UPDATED. |
| | |
| | 2) NOTE: PLEASE SEE THE NOTES GIVEN ON PREVIOUS REVIEW |
| | MENTIONED THE STATE OF FLORIDA INFORMATION DOES NOT |
| | MATCH WITH THE TITLE BLOCKS ON PLANS FOR THE |
| | ARCHITECTURAL FIRM. PLEASE SEE THAT THE PRINT OUT FROM |
| | THE STATE DEPARTMENT OF BUSINESS AND PROFESSIONAL |
| | REGULATION HAS BEEN ATTACHED TO NOTES ONCE AGAIN. |
| | PLEASE SEE THE LICENSE NUMBER FOR THE FIRM WHICH IS |
| | ALSO KNOW AS THE CERTIFICATE OF AUTHORIZATION NUMBER |
| | DOES NOT MATCH. |
| | FAC 61G1-16.004, FS 481.219 |
| | |
| | 3) NOTE: PLEASE INCLUDE CIRCUITING ON PLANS AND |
| | CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. |
| | PLEASE SEE THE ROOM AND AREA DESIGNATIONS ARE TO BE |
| | SHOWN ON PLANS FOR USE. |
| | PLEASE SEE THAT THE PANEL SCHEDULES ARE TO BE SPECIFIC |
| | TO ROOMS, AREAS AND EQUIPMENT IN WHICH THEY FEED. |
| | PLEASE SEE THE BELOW COMMENTARY TAKEN FROM THE NEC. |
| | |
| | |
| | 4) NOTE: PLEASE SEE THE SCOPE OF WORK FOR LIGHTING IS |
| | UNCLEAR AND WHETHER OR NOT COMPLIANCE WITH THE FBC |
| | CHAPTER 13 HAS BEEN MET. PLEASE SEE 13-101 FOR NEW, |
| | REPLACED WORK. PLEASE SEE 13-415.1.ABC.1.1, .1.2, |
| | 13-415.2 |
| | |
| | 5) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3(4) FOR |
| | MINIMUM LEVELS FOR FIRE ALARMS DEVICES TO BE STATED FOR |
| | ANY CHANGES. PLEASE SHOW ANY NEW EXISTING WHICH MEETS |
| | THIS SECTION WHERE WORK IS BEING AND CHANGES ARE BEING |
| | MADE. THIS WAS STATED ON PREVIOUS REVIEW. |
| | |
| | 6) NOTE: PLEASE INDICATE ALL EMERGENCY LIGHTING AND |
| | PROVIDE NEW OR EXISTING LIGHTING LEVELS FOR EGRESS |
| | PATHS. |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-33.004, |
| | NFPA-101 7.8, 7.9. |
| | PLEASE ALSO SEE NEC 700.12F FOR CIRCUITING OF THESE |
| | FIXTURES. PLEASE SEE POSSIBLE COMMENTS FROM THE FIRE |
| | MARSHAL. |
| | |
| | 7) NOTE: PLEASE VERIFY IT/SERVER ROOM AS NOTED ON PANEL |
| | SCHEDULE. SHOW ROOM AND COMPLIANCE WITH THE NEC 645.4, |
| | 645.10, 645.11 ETC. |
| | PLEASE SEE NFPA-75 FOR REQUIRED WALL RATINGS. NO |
| | HISTORY OF PERMITTING AND IT ROOM OFF AN INITIAL SEARCH |
| | COULD BE LOCATED. |
| | THIS MAY A FIELD VERIFICATION ITEM BEFORE ISSUANCE OF |
| | PERMIT. |
| | |
| | 8) NOTE: PLEASE KNOW THAT AS FOR INFORMATIONAL PURPOSE |
| | THE LV AS SHOWN ON PLANS WILL BE REQUIRED TO BE UNDER A |
| | SEPARATE PERMIT. THESE PLANS MAY BE USED FOR REFERENCE |
| | HOWEVER THE PERMIT APPLICATION AND FEES WILL BE |
| | SEPARATE. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |