| 2008-11-24 14:57:55 | REVISION DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | CITY WPB MUNICIPAL CODE |
| | |
| | ****FROM PREVIOUS REVISION REVIEW: |
| | |
| | 1. SHT MP-1 REVISION #5 INDICATED IN THE REVISION INDEX |
| | HAS NOT BEEN FOUND ON THE FLOOR PLAN. (THIS WAS A |
| | COMMENT FROM THE PREVIOUS REVISION SUBMITTED). SECTION |
| | 106.1.3. PLEASE INDICATE WHERE REVISION #5 IS ON THE |
| | FLOOR PLAN. SHOW WITH A CLOUD AND NUMBERED TRIANGLE. |
| | |
| | 2. SHT MP-1 MANY CHANGES DETECTED ON THE SHEET WITH NO |
| | CLOUDS OR NUMBERED TRIANGLES. ALL REVISIONS SHALL BE |
| | INDICATED WITH CLOUDS AND NUMBERED TRIANGLES. IF THERE |
| | ARE MANY REVISIONS THEN CLOUD THE COMPLETE FLOOR PLAN, |
| | BUT PLEASE INDICATE ALL REVISIONS. SECTION 106.1.3. |
| | |
| | 3. SHT MP-1 INDICATE IF THE 3 COMPARTMENT OR THE 2 |
| | COMPARTMENT SINKS ARE UTILIZIED FOR STORAGE, |
| | PREPARATION OR HANDLING OF FOOD. IF SO THE SINK/SINKS |
| | SHALL DISCHARGE THROUGH AN INDIRECT WASTE PIPE BY MEANS |
| | OF AN AIR GAP. SECTION 802.1.1. SECTION 106.1.2. |
| | |
| | 4. SHT MP-2 MANY REVISIONS/CHANGES SHOWN ON THE RISER |
| | DIAGRAMS ARE NOT CLOUDED OR NUMBERED. ALL REVISIONS |
| | SHALL BE INDICATED WITH CLOUDS AND NUMBERED TRIANGLES. |
| | SECTION 106.1.3. |
| | |
| | 5. SHT MP-2 WATER RISER DIAGRAM DOES NOT REFLECT THE |
| | FLOOR PLAN FOR THE SUPPLY PIPING TO THE DRINKING |
| | FOUNTAIN. THE FLOOR PLAN SHOWS THE WATER SUPPLY LOCATED |
| | THRU THE CABINETS, BUT THE RISER DIAGRAM SHOWS A DROP |
| | FROM THE CEILING ON THE RISER AT THE DRINKING FOUNTAIN. |
| | PLEASE CORRELATE. SECTIONS 106.1.1 & 601.1. |
| | |
| | 6. SHT MP-2 WATER RISER DIAGRAM. ALL HOSE BIBBS SHALL |
| | HAVE A SHUT OFF VALVE ON THE SUPPLY LINE TO THE HOSE |
| | BIBBS. SECTION 606.2(2). |
| | |
| | 7. SHT MP-2 SANITARY/GREASE RISER DIAGRAM. THE BYPASS |
| | LINE AT THE GREASE INTERCEPTOR IS NOT APPROVED AND DOES |
| | NOT REFLECT THE FLOOR PLAN. ARTICLE III SECTION |
| | 90-124(7) & SECTION 106.1.1. |
| | |
| | 8. SHT MP-2 SANITARY/GREASE RISER DIAGRAM. THE 2 |
| | COMPARTMENT SINK DRAIN LINE THAT USED TO CONNECT TO THE |
| | 3 COMPARTMENT SINK IS NOW A DEAD END. DEAD ENDS ARE NOT |
| | APPROVED. PLEASE DELETE OR USE FOR ONE SIDE OF THE 2 |
| | COMPARTMENT SINK SO IT CAN DRAIN INTO THE DRAIN LINE |
| | AND THE AAV REINSTALLED AT THE TOP OF THE LINE. SECTION |
| | 704.5. |
| | |
| | 9. SHT MP-2 SANITARY/GREASE RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN AT THE 2 COMPARTMENT SINK. THE |
| | FLOOR PLAN DOES NOT SHOW THE WASTE ARMS TO THE SINK |
| | TRAPS. |
| | |
| | (SEE COMMENTS FOR GAS REVIEW IN GAS STOP). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |