2008-09-09 09:03:29****CORRECTIONS****
 BUILDING REVISION
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE INCORPORATE ALL CHANGES INTO THE PLAN. FOR
 INSTANCE, SHEET 1 OF 3 CHANGES SHOULD BE INCORPORATED
 INTO THE LOWER ROOF FRAMING DETAIL, S1.
  
 2. THERE APPEAR TO BE SHEETS MISSING FROM THE REVISION.
 IT INCLUDES 1, 2, AND 3 OF 3, AND 1 OF 4. WHERE ARE 2
 THROUGH 4 OF 4?
  
 3. SEE SHEET S2 AND THE SIMPSON 2008 GENERAL CATALOG,
 PAGE 14, ITEM E. THE LINK IS INCLUDED BELOW AND IS
 PRINTED AND ATTACHED FOR YOUR CONVENIENCE. PLEASE
 CLARIFY THE COMBINED STRESS INDEX OF 92% STATED ON THE
 PLAN. IF ALL THREE LOADS ARE TAKEN INTO ACCOUNT AS PER
 THE CATALOG (AND THE CATALOG IN EFFECT AT TIME OF
 DESIGN), THE FORMULA EXCEEDS 1; IT RESULTS IN 1.53. IF
 UPLIFT AND PARALLEL AND UPLIFT AND PERPENDICULAR ARE
 TAKEN INTO ACCOUNT SEPARATELY, IT RESULTS IN 1.22 AND
 .97 RESPECTIVELY. IT IS NOT CLEAR HOW THE ENGINEER HAS
 ARRIVED AT A COMBINED STRESS INDEX OF 92%. PLEASE
 CLARIFY OR REVISE AS NECESSARY.
  
 HTTP://WWW.STRONGTIE.COM/FTP/CATALOGS/C-2008/C-2008-P01
 4.PDF
  
 4. SEE S2, PARALLEL TO TRUSS (F1) AND PERPENDICULAR TO
 TRUSS (F2), PLEASE NOTE THAT F1 IN THE SIMPSON CATALOG
 REFERS TO FORCES PARALLEL TO THE WALL, NOT PARALLEL TO
 TRUSS. F2 REFERS TO FORCES PERPENDICULAR TO THE WALL.
 PLEASE CLARIFY AND REVISE IF NECESSARY.
  
 5. PLEASE PROVIDE A VALUE FOR THE NEW WORK (FRAMING FOR
 SKYLIGHT, SKYLIGHT).
  
  