| Date |
Text |
| 2008-09-09 09:03:29 | ****CORRECTIONS**** |
| | BUILDING REVISION |
| | |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. PLEASE INCORPORATE ALL CHANGES INTO THE PLAN. FOR |
| | INSTANCE, SHEET 1 OF 3 CHANGES SHOULD BE INCORPORATED |
| | INTO THE LOWER ROOF FRAMING DETAIL, S1. |
| | |
| | 2. THERE APPEAR TO BE SHEETS MISSING FROM THE REVISION. |
| | IT INCLUDES 1, 2, AND 3 OF 3, AND 1 OF 4. WHERE ARE 2 |
| | THROUGH 4 OF 4? |
| | |
| | 3. SEE SHEET S2 AND THE SIMPSON 2008 GENERAL CATALOG, |
| | PAGE 14, ITEM E. THE LINK IS INCLUDED BELOW AND IS |
| | PRINTED AND ATTACHED FOR YOUR CONVENIENCE. PLEASE |
| | CLARIFY THE COMBINED STRESS INDEX OF 92% STATED ON THE |
| | PLAN. IF ALL THREE LOADS ARE TAKEN INTO ACCOUNT AS PER |
| | THE CATALOG (AND THE CATALOG IN EFFECT AT TIME OF |
| | DESIGN), THE FORMULA EXCEEDS 1; IT RESULTS IN 1.53. IF |
| | UPLIFT AND PARALLEL AND UPLIFT AND PERPENDICULAR ARE |
| | TAKEN INTO ACCOUNT SEPARATELY, IT RESULTS IN 1.22 AND |
| | .97 RESPECTIVELY. IT IS NOT CLEAR HOW THE ENGINEER HAS |
| | ARRIVED AT A COMBINED STRESS INDEX OF 92%. PLEASE |
| | CLARIFY OR REVISE AS NECESSARY. |
| | |
| | HTTP://WWW.STRONGTIE.COM/FTP/CATALOGS/C-2008/C-2008-P01 |
| | 4.PDF |
| | |
| | 4. SEE S2, PARALLEL TO TRUSS (F1) AND PERPENDICULAR TO |
| | TRUSS (F2), PLEASE NOTE THAT F1 IN THE SIMPSON CATALOG |
| | REFERS TO FORCES PARALLEL TO THE WALL, NOT PARALLEL TO |
| | TRUSS. F2 REFERS TO FORCES PERPENDICULAR TO THE WALL. |
| | PLEASE CLARIFY AND REVISE IF NECESSARY. |
| | |
| | 5. PLEASE PROVIDE A VALUE FOR THE NEW WORK (FRAMING FOR |
| | SKYLIGHT, SKYLIGHT). |
| | |
| | |