Plan Review Notes
Plan Review Notes For Permit 07071001
Permit Number 07071001
Review Stop P
Sequence Number 7
Notes
Date Text
2008-11-04 11:48:57REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
  
 1. SHT MP-1 REVISION #5 INDICATED IN THE REVISION INDEX
 HAS NOT BEEN FOUND ON THE FLOOR PLAN. (THIS WAS A
 COMMENT FROM THE PREVIOUS REVISION SUBMITTED). SECTION
 106.1.3. PLEASE INDICATE WHERE REVISION #5 IS ON THE
 FLOOR PLAN. SHOW WITH A CLOUD AND NUMBERED TRIANGLE.
  
 2. SHT MP-1 MANY CHANGES DETECTED ON THE SHEET WITH NO
 CLOUDS OR NUMBERED TRIANGLES. ALL REVISIONS SHALL BE
 INDICATED WITH CLOUDS AND NUMBERED TRIANGLES. IF THERE
 ARE MANY REVISIONS THEN CLOUD THE COMPLETE FLOOR PLAN,
 BUT PLEASE INDICATE ALL REVISIONS. SECTION 106.1.3.
  
 3. SHT MP-1 INDICATE IF THE 3 COMPARTMENT OR THE 2
 COMPARTMENT SINKS ARE UTILIZIED FOR STORAGE,
 PREPARATION OR HANDLING OF FOOD. IF SO THE SINK/SINKS
 SHALL DISCHARGE THROUGH AN INDIRECT WASTE PIPE BY MEANS
 OF AN AIR GAP. SECTION 802.1.1. SECTION 106.1.2.
  
 4. SHT MP-2 MANY REVISIONS/CHANGES SHOWN ON THE RISER
 DIAGRAMS ARE NOT CLOUDED OR NUMBERED. ALL REVISIONS
 SHALL BE INDICATED WITH CLOUDS AND NUMBERED TRIANGLES.
 SECTION 106.1.3.
  
 5. SHT MP-2 WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN FOR THE SUPPLY PIPING TO THE DRINKING
 FOUNTAIN. THE FLOOR PLAN SHOWS THE WATER SUPPLY LOCATED
 THRU THE CABINETS, BUT THE RISER DIAGRAM SHOWS A DROP
 FROM THE CEILING ON THE RISER AT THE DRINKING FOUNTAIN.
 PLEASE CORRELATE. SECTIONS 106.1.1 & 601.1.
  
 6. SHT MP-2 WATER RISER DIAGRAM. ALL HOSE BIBBS SHALL
 HAVE A SHUT OFF VALVE ON THE SUPPLY LINE TO THE HOSE
 BIBBS. SECTION 606.2(2).
  
 7. SHT MP-2 SANITARY/GREASE RISER DIAGRAM. THE BYPASS
 LINE AT THE GREASE INTERCEPTOR IS NOT APPROVED AND DOES
 NOT REFLECT THE FLOOR PLAN. ARTICLE III SECTION
 90-124(7) & SECTION 106.1.1.
  
 8. SHT MP-2 SANITARY/GREASE RISER DIAGRAM. THE 2
 COMPARTMENT SINK DRAIN LINE THAT USED TO CONNECT TO THE
 3 COMPARTMENT SINK IS NOW A DEAD END. DEAD ENDS ARE NOT
 APPROVED. PLEASE DELETE OR USE FOR ONE SIDE OF THE 2
 COMPARTMENT SINK SO IT CAN DRAIN INTO THE DRAIN LINE
 AND THE AAV REINSTALLED AT THE TOP OF THE LINE. SECTION
 704.5.
  
 9. SHT MP-2 SANITARY/GREASE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN AT THE 2 COMPARTMENT SINK. THE
 FLOOR PLAN DOES NOT SHOW THE WASTE ARMS TO THE SINK
 TRAPS.
  
 (SEE COMMENTS FOR GAS REVIEW IN GAS STOP).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  