Plan Review Notes
Plan Review Notes For Permit 07071001
Permit Number 07071001
Review Stop G
Sequence Number 5
Notes
Date Text
2008-11-04 12:05:49REVISION DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. -- REVISED RISER DIAGARM DOES NOT
 REFLECT THE FLOOR PLAN. FLOOR PLAN
 SHOWS THE GAS LINE INTO THE BUILDING AND AT THE FIRST
 RISER SHOWS NO PIPING TO THE RANGE, FRYERS ETC., BUT
 THE RISER DIAGRAM SHOWS A LINE BACK TO THE RANGE,
 FRYERS ETC. PLEASE CORRELATE.
  
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). -- NEW RISER ADDITION
 SHOWS THE MOST REMOTE OUTLET AT 65 FEET. PLEASE CHANGE
 INFORMATION.
  
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. -- THE PIPE SIZES
 ARE NOT CORRECT. 2" PIPE IS REQUIRED UP TO THE TEE PAST
 THE SHUT OFF VALVE AND THE EMERGENCY SHUT OFF VALVE.
 MINIMUM 1-1/4" IS REQUIRED UP TO THE DEEP FRYER. 1" IS
 REQUIRED UP TO THE SIMMERING COOKER. 1-1/4" IS REQUIRED
 TO THE WATER HEATER. 1" IS REQUIRED TO THE SINGLE RACK
 OVEN AND THE MINI RACK OVENS. PLEASE SHOW ALL CORRECT
 PIPE SIZES. TABLE 402.4(2).
  
 4. GAS PIPING SHALL BE SLEEVED AS IT ENTERS THE
 BUILDING. SECTION 404.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  