| Date |
Text |
| 2008-02-25 14:08:38 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 EXISTING BUILDING CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | ******FROM PREVIOUS REVIEWS: |
| | |
| | 1. ARCHITECTURAL SHEETS. THE PRINTED NAME OF THE PERSON |
| | SEALING THE DOCUMENT SHALL BE INDICATED IN THE TITLE |
| | BLOCK PER FAC 61G1-16.004(6) & FS 481.2055. |
| | ****RESPONSE NOTED, BUT DOES NOT ADDRESS THE COMMENT |
| | FOR THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT |
| | ON THE ARCHITECTURAL SHEETS. |
| | ******NO RESPONSE NOTED, BUT THE PRINTED NAME IS NOT |
| | SHOWN ON SHT A-4. |
| | |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | |
| | 5. SHT A-2DETAIL 1/A-2, THE TOILET ROOM SHALL BE |
| | ACCESSIBLE PER SECTION 806.1 OF THE EXISTING BUILDING |
| | CODE. SUBMIT DETAILS/ELEVATIONS SHOWING COMPLIANCE WITH |
| | SECTION 11-4.22 & ALL SUBSECTIONS. |
| | ****RESPONSE NOTED, BUT THE FOLLOWING HAS NOT BEEN |
| | ADDRESSED: |
| | ___FOR THE W/C: |
| | A. OK |
| | B. 11-4.16.5 FLUSH CONTROLS |
| | ******NO RESPONSE NOTED, NOT ADDRESSED. |
| | ___FOR THE URINAL: |
| | A. OK |
| | B. 11-4.18.4 FLUSH CONTROLS |
| | ******NO RESPONSE NOTED, NOT ADDRESSED. |
| | ___FOR THE LAV: |
| | A. OK |
| | B. OK |
| | |
| | 6. OK |
| | 7. OK |
| | 8. OK |
| | 9. OK |
| | 10. OK |
| | 11. OK |
| | 12. OK |
| | 13. OK |
| | 14. OK |
| | 15. OK |
| | 16. OK |
| | |
| | ********NEW COMMENTS********** |
| | (MISSED THE GAS REVIEW THE FIRST TIME THROUGH) |
| | |
| | 1B. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE |
| | FOLLOWING INFORMATION: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. RISER DOES NOT SHOW THE CUT LENGTH |
| | SECTIONS, NOR DOES IT REFLECT THE FLOOR PLAN. |
| | ******RESPONSE NOTED, BUT THE RISER STILL DOES NOT |
| | REFLECT THE FLOOR PLAN, NOR DOES THE RISER SHOW ALL THE |
| | CUT LENGTH SECTIONS. SEE THE SECTIONS THAT COME OFF THE |
| | METER VERTICALLY, TURN HORIZONTAL, DROP DOWN |
| | UNDERGROUND THEN TURN HORIZONTAL. ALSO THE SECTIONS OF |
| | PIPE THAT TURNS TOWARD THE BUILDING, UP PAST THE SHUT |
| | OFF VALVE, HORIZONTALL, THEN DROPS DOWN TO 4 FEET ABOVE |
| | THE FLOOR FOR THE KITCHEN APPLIANCES. ALSO SEE THE CUT |
| | SECTIONS OFF THE MAIN TO THE DOUBLE RACK OVEN AND THE |
| | CUT SECTIONS TO THE WATER HEATER. |
| | |
| | B. OK |
| | C. OK |
| | D. OK |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). (TO BE VERIFIED WHEN |
| | COMMENT A IS SUBMITTED). |
| | ******RESPONSE NOTED, BUT AS INDICATED IN THE LAST |
| | REVIEW, THIS WILL BE VERIFIED WHEN ALL CUT SECTIONS ARE |
| | GIVEN FOR COMMENT "A". |
| | |
| | F. OK |
| | |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ******RESPONSE NOTED, BUT NO MANUFACTURE SHEETS WERE |
| | SUBMITTED FOR THE STEAMER OR THE WATER HEATER. |
| | |
| | H. N/A |
| | I. N/A |
| | |
| | J. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | ******RESPONSE NOTED, BUT AN EMERGENCY HOOD SHUT DOWN |
| | SHUT OFF VALVE IS REQUIRED AS WELL AS A UNION EITHER |
| | BETEWEEN THE SHUT OFF VALVE AND THE EMERGNECY HOOD SHUT |
| | OFF VALVE OR DOWN STREAM OF THE EMERGENCY SHUT OFF |
| | VALVE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |