| 2008-02-01 14:42:01 | ** DENIED 3RD REVIEW ** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEWS ARE |
| | STILL IN NEED OF CORRECTIONS. PLEASE ALSO SEE THERE ARE |
| | NEW COMMENT(S) BASED ON INFORMATION NOW PLACED ON PLANS |
| | WHICH WAS NOT SHOWN PREVIOUSLY. |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS NOTE #1 WHICH SPECIFICALLY |
| | REQUESTED THE FOLLOWING CODES TO BE PLACED ON |
| | ELECTRICAL PLANS> |
| | THIS IS REQUIRED. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | |
| | ** MAY NOT QUOTE *LATEST EDITION* |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS REVIEWS WHICH REQUESTED |
| | NORMAL AND EMERGENCY PHOTO-METRIC LEVELS FOR STAIRS. |
| | THE LEVELS SUBMITTED AND SHOWN ON ARCHITECTURAL PLANS |
| | DO NOT MEET THE MINIMUM LEVELS AS SET-FORTH IN THE LIFE |
| | SAFETY CODE. PLEASE ALSO SEE ONLY ONE LEVEL WAS |
| | SUBMITTED. |
| | THIS WAS IN BOTH PREVIOUS REVIEWS. |
| | PLEASE SEE 7.8.1.3, 7.9.2.2 |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS REVIEWS REQUESTED TO |
| | COMPLETE WIRING FOR ALL OUTSIDE AND LANDSCAPE LIGHTING. |
| | NO SITE ELECTRICAL PLANS COULD BE LOCATED. |
| | PLEASE ALSO SEE SOME OUTSIDE LIGHTING IS NOW SHOWN ON A |
| | SINGLE POLE LIGHT SWITCH WHICH IS NOT PERMITTED. PLEASE |
| | SEE FBC CHAPTER 13, 13-415.1.ABC.1.4, 13-415.1.ABC.2 |
| | WHICH SPECIFICALLY REQUIRES AUTOMATED CONTROLS FOR |
| | OUTSIDE LIGHTING LEVELS. |
| | FOR EXAMPLE: OUTSIDE LIGHTS MAY NOT BE TURNED ON BE A |
| | SINGLE POLE SWITCH WHICH WILL LEAVE LIGHTS ON DURING |
| | DAYLIGHT HOURS AND CONDITIONS. THIS COMMENT IS FOR ALL |
| | LIGHTS OUTSIDE INCLUSIVE OF LANDSCAPE, PARKING, WALL |
| | LIGHTS, SIGN ETC. |
| | ** PLEASE SEE THERE IS STILL NOT ENOUGH |
| | PLEASE SEE PREVIOUS NOTES WITH RESPECT TO LIGHTING |
| | PERFORMANCE CALCULATIONS WHICH ARE NOT COMPLETE. THE |
| | FIRST REVIEW SUBMITTED METHOD *A* WHICH COULD NOT BE |
| | USED BASED ON THIS WAS NOT NEW CONSTRUCTION AND DID |
| | MEET THE DEFINITIONS OF RENOVATIONS. WHEN THIS IS THE |
| | CASE METHOD *B* OR *C* IS REQUIRED. PLEASE SEE THE |
| | PERMIT APPLICATION PACKAGE OF PLANS AND SUPPORTING |
| | DOCUMENTS SUBMITTED DID NOT CONTAIN ANY FLA-COM FORMS. |
| | THE LIGHTING LEVELS SHOWN ON SHEET E-1 DOES NOT CONTAIN |
| | THE INFORMATION FOR PERFORMANCE LEVELS AS NEEDED AND |
| | REQUIRED FOR MINIMUM COMPLIANCE WITH FBC 13-415.2, |
| | 13-415.1.B, 13-415.1.C, 13-400.0.C, 13-400.0.B, |
| | 13-400.3.B, 13-400.3.C, ETC |
| | PLEASE SEE NO EXTERIOR ALLOWANCES WERE SHOWN, PLEASE |
| | SEE 13-415.2.ABC.1.3 |
| | |
| | ***ATTENTION, PLEASE SEE FAC 61G15-33.004 WHICH |
| | REQUIRES THE ENGINEER OF RECORD TO DESIGN MINIMUM |
| | COMPLIANCE FOR ALL LIGHTING REQUIRED IN THE NEC< LS 101 |
| | AND FBC. |
| | |
| | 4) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH STATED THAT |
| | NEW *EQUIPMENT GROUNDING CONDUCTORS* WERE ADDED BEFORE |
| | THE FIRST MEANS OF DISCONNECT(S) WHICH IS NOT PERMITTED |
| | BY THE NEC. PLEASE SEE CODE SECTIONS 250.6, 250.24. |
| | PLEASE KNOW THE *EQUIPMENT GROUNDING CONDUCTORS* ARE |
| | ONLY INSTALLED *AFTER* THE FIRST MEANS OF DISCONNECT. |
| | AS SHOWN THIS WOULD CREATE OBJECTIONABLE CURRENTS AND A |
| | UNSAFE INSTALLATION. PLEASE REMOVE. |
| | |
| | 5) NOTE: PLEASE SEE THE COMPLETE GROUNDING ELECTRODE |
| | SYSTEM HAS NOW BEEN MOVED AND IS NOT IN COMPLIANCE WITH |
| | ANY SECTION OF NEC 250. |
| | PLEASE MOVE THIS GROUNDING ELECTRODE SYSTEM TO MEET |
| | NEC. |
| | PLEASE SEE REDLINED PLANS.THIS GEC AND SYSTEM SHALL |
| | BEAS FOLLOWS:: |
| | 1/0, 250.66, |
| | 2-GROUND RODS, 250.50, 250.56 |
| | COLD WATER PIPE, 250.50 |
| | GAS *** BOND ONLY***, 250.104 |
| | ** BUILDING STRUCTURAL FOOTER STEEL IS ONLY REQUIRED |
| | WHERE 20FT OR MORE IS AVAILABLE. PLEASE KNOW AS THIS IS |
| | AN EXISTING BUILDING AND IT DOES NOT APPEAR NEW FOOTERS |
| | OF 20FT OR MORE ARE NOT BEING INSTALLED, AN ATTACHMENT |
| | TO THE EXISTING IS NOT REQUIRED PER 250.50. IF THIS IS |
| | SHOWN ON THE GROUNDING ELECTRODE RISER THEN IT WILL BE |
| | REQUIRED. |
| | EXPOSING OLD/EXISTING FOOTER WOULD BE DETRIMENTAL TO |
| | THE STRUCTURAL INTEGRITY OF THE EXISTING FOOTERS. |
| | |
| | ** IMPORTANT** PLEASE CALL TO GO OVER THIS AS THERE IS |
| | SOME LOSS IN UNDERSTANDING FROM THE COMMENTS TO WHAT IS |
| | BEING DONE ON PLANS. THIS IS FOR COMMENT #4 AND 5. |
| | |
| | 6) NOTE: PLEASE SEE A NEW NOTE WAS ADDED TO E-2 HOWEVER |
| | WAS NOT PER THE PREVIOUS NOTES OF 13-413.1.ABC.2.1 AND |
| | .2.2. |
| | |
| | 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | PLEASE SEE THAT A FEE OF $3, 408 IS DUE BEFORE |
| | RE-SUBMITTAL OF PLANS. THIS IS NOT ASSESSED TO THE |
| | CONTRACTOR OR OWNER. |
| | ONE SET OF PLANS WILL BE RETAINED BY THIS OFFICE. |
| | |
| | 8) NOTE: PLEASE SEE FS 713.13(2), THE NOTICE OF |
| | COMMENCEMENT SUBMITTED IS EXPIRED. |
| | WHEN WORK HAS NOT COMMENCED WITHIN 90DAYS OF RECORDING |
| | NOC, THE NOC BECOMES VOID AND WILL BE REQUIRED TO BE |
| | RE-RECORDED. |
| | |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |