| 2008-02-14 12:27:26 | ****CORRECTIONS**** |
| | |
| | |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | COMMENTS FROM PREVIOUS LIST |
| | |
| | 1.INDICATE LEVEL OF ALTERATION, FBC EB301.5. |
| | |
| | LEVEL 2 DECLARED.PLEASE CLARIFY; WORK AREA IS OVER |
| | 50% OF THE BUILDING, THEREFORE APPEARS TO BE A LEVEL 3. |
| | SEE FBC EB CHAPTER 3. |
| | |
| | 2-6.)ADDRESSED. |
| | |
| | 7.I WAS UNABLE TO LOCATE THE SPIRAL STAIR SHOPS. |
| | PLEASE HAVE THE ARCHITECT INCORPORATE DESIGN INTO THE |
| | PLAN, FBC1009.9. |
| | |
| | 3RD REVIEW; SHOPS DO NOT SHOW CODE COMPLIANCE WITH ALL |
| | REQUIREMENTS OF FBC1009.9.PLEASE INCORPORATE ALL |
| | REQUIRED DESIGN CRITERIA INTO THE PLAN. |
| | |
| | NOTE THE FOLLOWING: |
| | |
| | A.FBC1009.9.1, RISER HEIGHT IS NOT TO EXCEED 7". |
| | FBC1009.9.2 DOES NOT APPLY BECAUSE THIS IS NOT A |
| | MEZZANINE, FLOOR AREA EXCEEDS 250', AND OCCUPANT LOAD |
| | SHOULD BE 4.9 1/2" RISER HEIGHT HAS BEEN SPECIFIED, |
| | PLEASE REVISE. |
| | |
| | B.SHOW COMPLIANCE WITH FBC1009.9.1 (2) AND (3) |
| | REGARDING TREAD DEPTH.A 12" DIMENSION WAS SHOWN BUT |
| | PURPOSE OF THIS DIMENSION IS NOT CLEAR. |
| | |
| | C.FBC1009.9.1 (4), INSIDE HANDRAIL NOT SHOWN. PROVIDE |
| | A HANDRAIL DETAIL IN COMPLIANCE WITH FBC1009.1(4) AND |
| | (5).NO HANDRAIL EXTENSIONS ARE SHOWN. |
| | |
| | D.A LINE WHICH APPEARS TO GRAPHICALLY SHOW THE |
| | HANDRAIL TO THE OUTSIDE OF THE STAIR GOES ACROSS THE |
| | STAIR TREAD.WHAT IS THIS? |
| | |
| | E.VERTICAL ACCESSIBILITY CAN BE EXEMPTED |
| | FBC11-4.1.6(1)(K)(III), A SPACE NOT OPEN TO THE PUBLIC |
| | AND AN OCCUPANT LOAD OF LESS THAN 5.PLEASE MAKE NOTE |
| | ON THE PLAN THAT THIS AREA IS NOT OPEN TO THE PUBLIC. |
| | HOWEVER, EXEMPTION FROM VERTICAL ACCESSIBILITY |
| | REQUIREMENTS DOES NOT WAIVE OTHER REQUIREMENTS FOR |
| | ACCESSIBILITY.SEE FBC11-4.1.6(1)(A) AND (B).SEE |
| | HANDRAIL HEIGHT AND EXTENSION REQUIREMENTS OF |
| | FBC1009.11, FBC11-4.8.5.PROVIDE GUADRAIL AND HANDRAIL |
| | DETAILS. |
| | |
| | 8.ROOF FRAMING ENGINEERING WAS SUBMITTED.THE |
| | STRUCTURAL ENGINEER HAS SPECIFIED DESIGN CRITERIA OF |
| | EXPOSURE C (S2) AND A BCLL OF 10PSF (SEE WOOD TRUSS |
| | NOTES).THE TRUSS ENGINEER HAS STATED THAT A |
| | NONCURRENT LIVE LOAD OF 10PSF HAS BEEN CHECKED, BUT THE |
| | ENGINEERING IS FOR 0 BCLL.PLEASE CORRELATE STRUCTURAL |
| | DESIGN WITH THE TRUSS ENGINEERING, REVISE AS NECESSARY, |
| | AND HAVE THE TRUSS ENGINEERING REVIEWED BY DESIGNER OF |
| | RECORD. |
| | |
| | 9-13. ADDRESSED. |
| | |
| | 14.ARCHITECT STATES IN HIS RESPONSE LETTER (AND ON |
| | A1) THAT OCCUPANT LOAD IS LESS THAN 3 FOR THE SECOND |
| | FLOOR.SEE FBC1004.1, OCCUPANT LOAD CANNOT BE LESS |
| | THAN FBC TABLE 1004.SEE OTHER COMMENTS REGARDING |
| | OCCUPANT LOAD. |
| | |
| | 3RD REVIEW, SEE 2ND FLOOR.WHEN SCALED, THE INTERIOR |
| | DIMENSIONS ARE 23' (24'6"-16") BY 14.33'(15'8"-16"); |
| | 332 SF, OCCUPANT LOAD OF 4.ALL NUMBERS SHOULD BE |
| | ROUNDED UP TO THE NEAREST WHOLE NUMBER AS THE OCCUPANT |
| | LOAD CANNOT BE LESS THAN TABLE 1004 AND YOU CANNOT HAVE |
| | A PORTION OF A PERSON.REVISE OCCUPANT LOAD |
| | ACCORDINGLY. |
| | |
| | 15-22. ADDRESSED. |
| | |
| | 23.PLEASE REVISE OCCUPANCY AND OCCUPANT LOAD FOR |
| | SECOND FLOOR AS DISCUSSED WITH ARCHITECT. |
| | |
| | 3RD REVIEW, SEE ITEM 14. |
| | |
| | 24-25.)ADDRESSED. |
| | |
| | 26.A1, OCCUPANT LOAD CANNOT BE LESS THAN FBC TABLE |
| | 1004 AS PER FBC1004.1.THE TOTAL SQUARE FOOT AREA USED |
| | TO CALCULATE OCCUPANT LOAD IS NOT CONSISTENT WITH THE |
| | SQUARE FOOT AREA OF THE SPACE.PLEASE REVISE. |
| | |
| | SEE OTHER COMMENTS REGARDING OCCUPANT LOAD. |
| | |
| | 27.ADDRESSED. |
| | |
| | 28.INCLUDE 2007 AMENDMENTS IN GOVERNING CODE |
| | EFFECTIVE JULY 1, 2007. |
| | |
| | PLEASE REVISE STRUCTURAL SHEETS.THIS PROJECT IS |
| | AFFECTED BY 2007 REVISIONS. |
| | |
| | 29.ADDRESSED. |
| | |
| | NEW COMMENTS: |
| | |
| | 30.PLEASE PROVIDE FLORIDA STATE PRODUCT APPROVAL FOR |
| | ALL PRODUCTS, IF AVAILABLE.WWW.FLORIDABUILDING.ORG. |
| | THIS IS REQUIRED IN ADDITION TO THE MIAMIDADE NOAS |
| | PROVIDED, FAC9B72. |
| | |
| | 31.THE SMITH MOUNTAIN WINDOW IS SMALL MISSILE IMPACT |
| | RATED; LARGE MISSILE REQUIRED, FBC1609.1.4. |
| | |
| | 32.WHERE WILL THE WOOD INFILL FRAMING DETAIL BE |
| | INSTALLED, S3? |